<p><strong>The Model CDD Duct Mount Carbon Dioxide Transmitter </strong> monitors the occupancy in a room by detecting the concentration of carbon dioxide in the return air duct. The non-dispersive infrared sensing technology automatically updates the calibration of the transmitter using a proprietary logic feature which limits the amount of error due to drift. The Model CDD can measure up to 2000 PPM in duct air flows less than 1500 FPM. </p> <strong>Product Applications </strong> <ul> <li>On demand room ventilation. </li> </ul>

Attributes

Key ^Value
Accuracy?40 PPM + 3% of reading @ 22 ?C.
Ambient Operating Temperature32 to 122 ?F (0 to 50 ?C).
Duct Air Velocity Range0 to 1500 FPM (7.63 m/s).
HousingFlammability Classification UL rated 94V-5VA.
Non-Linearity< 1% of FS.
Outputs0 to 10 VDC.
Power Requirements18 to 30 VAC RMS 50/60 Hz or 18 to 42 VDC.
Pressure Dependence0.13% of reading per mm of Hg.
Range0 to 2000 PPM.
Response Time3 minutes typical for 90% step change.
Stability< 2% of FS over life of sensor.
Storage Temperature-4 to 158 ?F (-20 to 70 ?C).
Temperature Dependence0.2% FS per ?C.