| Action | Nonreversing |
| Amps AC | 270 |
| Auxiliary Contact Form | 1NO |
| Coil Volts | 120V AC |
| Country of Origin (subject to change) | Dominican Republic |
| Depth | 22 in |
| Enclosure NEMA Rating | No Enclosure |
| Features | Class 20 Solid State Ambient-Compensated Overload Relay and Instantaneous Magnetic Trip Mechanism, with Ground Fault |
| Height | 9.5 in |
| HP @ 3 Phase - 208V | 75 hp |
| HP @ 3 Phase - 240V | 100 hp |
| HP @ 3 Phase - 480V, HP @ 3 Phase - 575V | 200 hp |
| Hz | 50/60 |
| Includes | Class 20 Solid State Ambient-Compensated Overload Relay and Instantaneous Magnetic Trip Mechanism, W/ Ground Fault |
| Item, Product Type | NEMA Magnetic Motor Starter |
| NEMA Size | 5 |
| Number of Poles | 3 |
| Overload Relay Amp Setting | 60 to 300A |
| Standards | UL, CSA, CE, NEMA, IEC/EN 60947 VDE 0660, ISO 13849-1 (EN954-1), RoHS, ATEX directive 94/9/EC, Equipment Group 2, Category 2 |
| Starter Type | NEMA Style |
| Width | 12.5 in |