prev
Mayer Electric Supply LC1K12004T7
Mayer Electric Supplyzoom

Attributes

Key ^Value
[Icw] rated short-time withstand current25 A = 15 s power circuit, 50 A 55 A 75 A 100 A 105 A 115 A
[Ie] rated operational current16 A ( 20 A (
[Ith] conventional free air thermal current20 A at
[Ue] rated operational voltage690 V AC 50/60 Hz for power circuit
[Ui] rated insulation voltage600 V for power circuit conforming to UL 508, 600 V for power circuit conforming to CSA C22.2 No 14, 690 V for power circuit conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage8 kV
Ambient air temperature for operation-13...122 ?F (-25...50 ?C)
Ambient air temperature for storage-58...176 ?F (-50...80 ?C)
Associated fuse rating25 A aM for power circuit, 25 A gG at
Average impedance3 mOhm at 50 Hz - Ith 20 A for power circuit
Category22326 - CTR,K-LINE,AC,OPEN,NONREV
Commercial StatusCommercialised
Connections - terminals : Screw clamp terminals 1 cable(s) 0...0 in? (0.34...2.5 mm?) - cable stiffness, Connections - terminals : Screw clamp terminals 2 cable(s) 0...0 in? (0.34...1.5 mm?) - cable stiffnessflexible - with cable end
Connections - terminals : Screw clamp terminals 1 cable(s) 0...0.01 in? (0.75...4 mm?) - cable stiffness, Connections - terminals : Screw clamp terminals 2 cable(s) 0...0.01 in? (0.75...4 mm?) - cable stiffnessflexible - without cable end
Connections - terminals : Screw clamp terminals 1 cable(s) 0...0.01 in? (1.5...4 mm?) - cable stiffness, Connections - terminals : Screw clamp terminals 2 cable(s) 0...0.01 in? (1.5...4 mm?) - cable stiffnesssolid
Contactor applicationResistive load
Control circuit typeAC 50/60 Hz
Control circuit voltage480 V AC 50/60 Hz
Control circuit voltage limits0.2...0.75 Uc at 0.8...1.15 Uc at
Country of originFR
Depth2.24 in (57 mm)
Device short nameLC1K
Discount ScheduleI12
Electrical durability0.3 Mcycles 20 A AC-1 at Ue
Flame retardanceRequirement 2 conforming to NF F 16-101, Requirement 2 conforming to NF F 16-102, V1 conforming to UL 94
GTIN00785901790143
Heat dissipation1.3 W
Height2.28 in (58 mm)
Hold-in power consumption in VA4.5 VA at 68 ?F (20 ?C)
Inrush power in VA30 VA at 68 ?F (20 ?C)
IP degree of protectionIP2x conforming to VDE 0106
Irms rated making capacity144 A AC for power circuit conforming to IEC 60947, 144 A AC for power circuit conforming to NF C 63-110
Mechanical durability10 Mcycles
Mechanical robustnessShocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27, Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27, Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27, Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27, Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27, Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27, Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6, Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
Mounting supportPlate, Rail
Nbr. of units in pkg.1
Operating altitude6561.68 ft (2000 m) without derating in temperature
Operating rate3600 cyc/h
Operating time10...20 ms coil energisation and NO closing, 10...20 ms coil de-energisation and NO opening
Overvoltage categoryIII
Package weight(Lbs)0.40
Period18 months
Pole contact composition4 NO
Poles description4P
Product availabilityNon-Stock - Not normally stocked in distribution facility
Product certificationsUL, CSA
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable, Download?Product environmental
Product or component typeContactor
Product weight0.4 lb(US) (0.18 kg)
Protective treatmentTC conforming to DIN 50016, TC conforming to IEC 60068
Range of productTeSys K
Rated breaking capacity70 A at 660...690 V conforming to IEC 60947, 110 A at 440 V conforming to IEC 60947, 80 A at 500 V conforming to IEC 60947
REAChReference not containing SVHC above the threshold
ReturnabilityN
RoHSSchneider Electric declaration of conformity, Compliant - since 0640 -
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
StandardsBS 5424, NF C 63-110, IEC 60947, VDE 0660
Sustainable offer statusGreen Premium product
Tightening torque11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat ? 6 mm, 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2
Utilisation categoryAC-1
Width1.77 in (45 mm)