[Ipk] Rated Peak Withstand Current | 1.03 kA |
[Uimp] Rated Impulse Withstand Voltage | 10 kV |
Ambient Air Temperature For Operation | 40-40 ?C |
Average Ambient Air Temperature For Operation | 30 ?C |
Box Number | 18M |
California Proposition 65 : WARNING: This product can expose you to chemicals including | Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Continuous Thermal Current Rating Factor | 405 16.6 % || 509 25 % || 1075 50 % || 2017 75 % || 3337 100 % |
Degree Of Protection | UL type 2 || UL type 3R, with 7400WS18M19M20M |
Depth | 627 mm |
Device Application | low voltage electrical distribution |
Device Short Name | DOE 2016 |
Efficiency | 98.30 % at 35 % load factor , 75.0 ?C |
Electrical Connection | 2 Hole Nema Pad secondary 11.1 mm || 4 Hole Nema Pad sec - XO 11.1 mm || 2 Hole Nema Pad primary 11.1 mm |
Environmental Disclosure | ENVPEP1604028EN |
Eu Rohs Directive | Compliant |
Halogen Content Performance | Halogen free plastic parts product |
Height | 719 mm |
Inrush Current | 532 A |
Material | aluminium |
Mercury Free, Pvc Free, Reach Free Of Svhc, Rohs Exemption Information, Toxic Heavy Metal Free | Yes |
Mounting Support | floor || floor, with 7400FMB || ceiling, with 7400CMB18M19M20M || wall, with 7400WMB18M19M20M |
Net Weight | 151.05 kg |
Network Frequency | 60 Hz |
Noise Level | 6 dB NEMA ST-20 || 39 dB |
Number Of Mounting Holes | 13 mm |
Number Of Tap-Offs | 2 2.5 % FCAN || 4 2.5 % FCBN |
Percentage Impedance Voltage | 3.50 % |
Percentage Reactance | 1.96 % |
Phase | 3 phase |
Primary Operational Current | 36.08-36.08 A 36.08 A 30 kVA |
Primary Voltage | 480 V delta |
Product Or Component Type | DOE 2016 energy efficient transformer |
Range Of Product | Square D |
Rated Operational Power In Va | 30 kVA |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
Secondary Voltage | 480Y/277 V |
Standards | UL 1561 || CSA C22.2 No 47 || NEMA ST-20 |
Sustainable Offer Status | Green Premium product |
Tap Loss | 94 no load (core loss) || 884 load loss (coil loss) |
Temperature Rise | 150 ?C || 220 ?C insulated |
Transformer Type | energy efficient |
Type Of Cooling | natural convection |
Width | 648 mm |
X/R Ratio | 0.78 |