| [Ue] Rated Operational Voltage | 24 V DC |
| Ambient Air Temperature For Operation | -10-60 ?C |
| Ambient Air Temperature For Storage | -25-85 ?C |
| Analogue Input Number | 4 |
| Analogue Input Resolution | 16 bits |
| Analogue Input Type | KTY 84 silicon temperature probe || KTY 10 silicon temperature probe || Pt 1000 temperature probe || Pt 100 temperature probe |
| Bus Type | TM7 bus |
| California Proposition 65 : WARNING: This product can expose you to chemicals including | Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
| China Rohs Regulation | X |
| Circularity Profile | ENVEOLI1409005EN |
| Disturbance Radiated/Conducted | CISPR 11 |
| Electrical Connection | 1 male connector M12 - B coding - 4 ways bus IN || 1 female connector M12 - B coding - 4 ways bus OUT || 4 female connectors M12 - A coding - 5 ways sensor || 1 male connector M8 - 4 ways power IN || 1 female connector M8 - 4 ways power OUT |
| Electromagnetic Compatibility | EN/IEC 61000-4-6 |
| Enclosure Material | Plastic |
| Environmental Disclosure | ENVPEP1409005EN |
| Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
| Fixing Mode | by 2 screws |
| Input Impedance | 0...3276 Ohm |
| Input/Output Number | 4 |
| Input/Output Number Of Splitter Box | 4 I |
| Ip Degree Of Protection | IP67 conforming to IEC 61131-2 |
| Local Signalling | for bus diagnostic 2 LEDs || for sensor/actuator power supply status 2 LEDs |
| Marking | CE |
| Mercury Free | Yes |
| Net Weight | 0.2 kg |
| Operating Altitude | 0...6561.68 ft (0...2000 m) |
| Operating Position | any position |
| Pollution Degree | 2 IEC 60664 |
| Product Certifications | GOST-R || ATEX II 3g EEx nA II T5 || cURus || C-tick |
| Product Or Component Type | analog I/O expansion block |
| Pvc Free | Yes |
| Range Compatibility | Modicon M258 || Modicon LMC058 |
| Range Of Product | Modicon TM7 |
| Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
| Relative Humidity | 5-95 % without condensation or dripping water |
| Resistance To Electromagnetic Fields | 10 V/m 0.08-2 Hz EN/IEC 61000-4-3 || 1 V/m 2-2.7 Hz EN/IEC 61000-4-3 |
| Resistance To Electrostatic Discharge | 6 kV in contact EN/IEC 61000-4-2 || 8 kV in air EN/IEC 61000-4-2 |
| Resistance To Fast Transients | 2 kV EN/IEC 61000-4-4 power supply) || 1 kV EN/IEC 61000-4-4 input/output) || 1 kV EN/IEC 61000-4-4 shielded cable) |
| Rohs Exemption Information | Yes |
| Sensor Power Supply | 24-24 V overload, short-circuit and reverse polarity protection |
| Shock Resistance | 30 gn 11 ms IEC 60721-3-5 Class 5M3 |
| Standards | IEC 61131-2 |
| Storage Altitude | 0-3000 m |
| Surge Withstand | 1 kV power supply (common mode) EN/IEC 61000-4-5 || 0.5 kV power supply (differential mode) EN/IEC 61000-4-5 || 1 kV unshielded links (common mode) EN/IEC 61000-4-5 || 0.5 kV unshielded links (differential mode) EN/IEC 61000-4-5 || 1 kV shielded links (common mode) EN/IEC 61000-4-5 || 0.5 kV shielded links (differential mode) EN/IEC 61000-4-5 |
| Sustainable Offer Status | Green Premium product |
| Toxic Heavy Metal Free | Yes |
| Vibration Resistance | 7.5 mm constant amplitude 2-8 Hz)IEC 60721-3-5 Class 5M3 || 2 gn constant acceleration 8-200 Hz)IEC 60721-3-5 Class 5M3 || 4 gn constant acceleration 200-500 Hz)IEC 60721-3-5 Class 5M3 |
| Warranty | 18 months |
| Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |