mpn
LC1D096BD
brand
name: SCHNEIDER ELECTRIC
manufacturer
name: SCHNEIDER ELECTRIC
Attributes
Key
Value
[Icw] Rated Short-Time .
105 A 40 ?C - 10 s powe.
[Ith] Conventional Free.
25 A 60 ?C power circui.
[Uc] Control Circuit Vo.
24 V DC
[Ui] Rated Insulation V.
power circuit 690 V IEC.
[Uimp] Rated Impulse Wi.
6 kV IEC 60947
Auxiliary Contact Compo.
1 NO + 1 NC
Auxiliary Contacts Type
mechanically linked 1 N.
Average Impedance
2.5 mOhm - Ith 25 A 50 .
California Proposition .
Antimony oxide & Antimo.
China Rohs Regulation
Product out of China Ro.
Circularity Profile
ENVEOLI1102030EN
Climatic Withstand
IACS E10 exposure to da.
Coil Technology
built-in bidirectional .
Compatibility Code
LC1D
Connections - Terminals
control circuit lugs-ri.
Contact Compatibility
M4
Contactor Application
motor control || resist.
Control Circuit Type
DC standard
Control Circuit Voltage.
0.1...0.25 Uc -40-70 ?C.
Depth
95 mm
Device Short Name
LC1D
Environmental Disclosure
ENVPEP110230EN
Eu Rohs Directive
Compliant
Fire Resistance
850 ?C IEC 60695-2-1
Flame Retardance
V1 conforming to UL 94
Height
77 mm
Hold-In Power Consumpti.
5.4-5.4 W 20 ?C
Inrush Power In W
5.4-5.4 W 20 ?C)
Insulation Resistance
> 10 MOhm signalling ci.
Ip Degree Of Protection
IP20 front face IEC 605.
Irms Rated Making Capac.
250 A 440 V power circu.
Maximum Horse Power Rat.
1 hp 230/240 V at AC 50.
Maximum Operating Rate
3600 cyc/h 60 ?C
Mechanical Durability
30 Mcycles
Mechanical Robustness
vibrations contactor op.
Mercury Free
Yes
Minimum Switching Curre.
5 mA signalling circuit
Minimum Switching Volta.
17 V signalling circuit
Motor Power Kw
2.2 kW 220...230 V AC 5.
Mounting Support
plate || rail
Net Weight
0.48 kg
Non-Overlap Time
1.5 ms on de-energisati.
Operating Altitude
0...9842.52 ft (0...300.
Operating Time
53.55...72.45 ms closin.
Overvoltage Category
III
Permissible Ambient Air.
-40-60 ?C || 60-70 ?C w.
Pole Contact Composition
3 NO
Poles Description
3P
Pollution Degree
3
Power Dissipation Per P.
1.56 W AC-1 || 0.2 W AC.
Product Certifications
CCC || RINA || BV || CS.
Product Or Component Ty.
contactor
Protective Cover
with
Protective Treatment
THIEC 60068-2-30
Pvc Free
Yes
Range Of Product
TeSys Deca
Rated Breaking Capacity
250 A 440 V power circu.
Reach Regulation
Reference contains Subs.
Rohs Exemption Informat.
Yes
Safety Reliability Level
B10d = 1369863 cycles c.
Signalling Circuit Freq.
25...400 Hz
Standards
CSA C22.2 No 14 || EN 6.
Sustainable Offer Status
Green Premium product
Tightening Torque
control circuit 1.7 N.m.
Time Constant
28 ms
Utilisation Category
AC-3 || AC-4 || AC-1 ||.
Warranty
18 months
Width
45 mm