Attributes

Key Value
[Icw] Rated Short-Time .105 A 40 ?C - 10 s powe.
[Ith] Conventional Free.25 A 60 ?C power circui.
[Uc] Control Circuit Vo.72 V DC
[Ui] Rated Insulation V.power circuit 690 V IEC.
[Uimp] Rated Impulse Wi.6 kV IEC 60947
Ambient Air Temperature.-40-60 ?C || 60-70 ?C w.
Ambient Air Temperature.-60-80 ?C
Auxiliary Contact Compo.1 NO + 1 NC
Auxiliary Contacts Typemechanically linked 1 N.
Average Impedance2.5 mOhm - Ith 25 A 50 .
California Proposition .Antimony oxide & Antimo.
China Rohs RegulationProduct out of China Ro.
Circularity ProfileENVEOLI1501004
Climatic WithstandIACS E10 || IEC 60947-1.
Coil Technologybuilt-in bidirectional .
Connections - Terminalscontrol circuit lugs-ri.
Contactor Applicationresistive load || motor.
Control Circuit TypeDC low consumption
Control Circuit Voltage.0.1...0.3 Uc -40-70 ?C .
Depth95 mm
Device Short NameLC1D
Environmental DisclosureENVPEP1501004
Eu Rohs DirectiveCompliant
Fire Resistance850 ?C IEC 60695-2-1
Height77 mm
Hold-In Power Consumpti.2.4-2.4 W 20 ?C
Inrush Power In W2.4-2.4 W 20 ?C)
Insulation Resistance> 10 MOhm signalling ci.
Ip Degree Of ProtectionIP20 front face IEC 605.
Irms Rated Making Capac.250 A 440 V power circu.
Maximum Horse Power Rat.1 hp 230/240 V at AC 50.
Maximum Operating Rate3600 cyc/h 60 ?C
Mechanical Durability30 Mcycles
Mechanical Robustnessvibrations contactor op.
Mercury FreeYes
Minimum Switching Curre.5 mA signalling circuit
Minimum Switching Volta.17 V signalling circuit
Motor Power Kw2.2 kW 220...230 V AC 5.
Mounting Supportplate || rail
Net Weight0.48 kg
Non-Overlap Time1.5 ms on de-energisati.
Operating Altitude0...9842.52 ft (0...300.
Operating Time65.45...88.55 ms closin.
Overvoltage CategoryIII
Pole Contact Composition3 NO
Poles Description3P
Pollution Degree3
Power Dissipation Per P.1.56 W AC-1 || 0.2 W AC.
Product CertificationsGOST || DNV || LROS (Ll.
Product NameTeSys D || TeSys Deca
Product Or Component Ty.contactor
Protective Coverwith
Protective TreatmentTH IEC 60068-2-30
Pvc FreeYes
RangeTeSys || TeSys Deca
Rated Breaking Capacity250 A 440 V power circu.
Reach RegulationReference contains Subs.
Rohs Exemption Informat.Yes
Safety Reliability LevelB10d = 1369863 cycles c.
Signalling Circuit Freq.25...400 Hz
StandardsCSA C22.2 No 14 || EN 6.
Sustainable Offer StatusGreen Premium product
Tightening Torquecontrol circuit 1.7 N.m.
Time Constant40 ms
Toxic Heavy Metal FreeYes
Utilisation CategoryAC-1 || AC-4 || AC-3 ||.
Warranty18 months
Width45 mm
prev