[Icw] Rated Short-Time Withstand Current | 115 A 50 ?C - 1 s power circuit || 105 A 50 ?C - 5 s power circuit || 100 A 50 ?C - 10 s power circuit || 75 A 50 ?C - 30 s power circuit || 55 A 50 ?C - 1 min power circuit || 50 A 50 ?C - 3 min power circuit || 25 A 50 ?C - >= 15 min power circuit |
[Ith] Conventional Free Air Thermal Current | 20 A 60 ?C power circuit || 10 A 50 ?C signalling circuit |
[Uc] Control Circuit Voltage | 230 V AC 50/60 Hz |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Average Impedance | 3 mOhm - Ith 20 A 50 Hz power circuit |
California Proposition 65 : WARNING: This product can expose you to chemicals including | Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Circularity Profile | ENVEOLI1503003EN |
Connections - Terminals | screw clamp terminals 1 1.5-4 mm?solid || screw clamp terminals 1 0.75-4 mm?flexible without cable end || screw clamp terminals 1 0.34-2.5 mm?flexible with cable end || screw clamp terminals 2 1.5-4 mm?solid || screw clamp terminals 2 0.75-4 mm?flexible without cable end || screw clamp terminals 2 0.34-1.5 mm?flexible with cable end |
Contactor Application | resistive load |
Control Circuit Type | AC 50/60 Hz |
Control Circuit Voltage Limits | operational 0.8...1.15 Uc 50 ?C) || drop-out >= 0.20 Uc 50 ?C) |
Depth | 57 mm |
Device Application | control |
Environmental Disclosure | ENVPEP1503003EN |
Eu Rohs Directive | Compliant |
Flame Retardance | V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102 |
Heat Dissipation | 1.3-1.3 W |
Height | 58 mm |
Hold-In Power Consumption In Va | 4.5-4.5 VA 20 ?C) |
Inrush Power In Va | 30-30 VA 20 ?C) |
Irms Rated Making Capacity | 144 A AC power circuit IEC 60947 |
Maximum Operating Rate | 3600 cyc/h |
Mechanical Durability | 10 Mcycles |
Mechanical Robustness | shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 |
Mercury Free, Reach Free Of Svhc, Rohs Exemption Information, Toxic Heavy Metal Free | Yes |
Operating Altitude | 6561.68 ft (2000 m) without derating |
Operating Time | 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing |
Overvoltage Category | III |
Pole Contact Composition | 4 NO |
Poles Description | 4P |
Product Certifications | CB Scheme || CCC || UL || CSA || EAC || CE || UKCA |
Product Or Component Type | contactor |
Protective Treatment | TC IEC 60068 || TC DIN 50016 |
Range | TeSys |
Rated Breaking Capacity | 110 A 440 V IEC 60947 || 80 A 500 V IEC 60947 || 70 A 660...690 V IEC 60947 |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Standards | EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 |
Sustainable Offer Status | Green Premium product |
Utilisation Category | AC-1 |
Warranty | 18 months |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Width | 45 mm |