3-Phase HP Rating (Max.) | 15 hp |
[Icw] Rated Short-Time Withstand Current | 40 A 40 ?C - 10 min for power circuit || 84 A 40 ?C - 1 min for power circuit || 145 A 40 ?C - 10 s for power circuit || 240 A 40 ?C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit |
[Ith] Conventional Free Air Thermal Current | 10 A (at 60 ?C) for signalling circuit || 32 A (at 60 ?C) for power circuit |
[Uc] Control Circuit Voltage, Coil Voltage | 24 V AC 50/60 Hz |
[Ui] Rated Insulation Voltage | power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL |
[Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
Action, Contactor Type | Reversing |
Ambient Air Temperature For Operation | -40-60 ?C || 60-70 ?C with derating |
Ambient Air Temperature For Storage | -60-80 ?C |
Application | Resistive load;motor control |
Approval | CSA, EN, IEC, UL, DNV, CCC, GL, LROS, BV, RINA, GOST, UKCA |
Auxiliary Contact Composition, Contact Configuration | 1 NO + 1 NC |
Auxiliary Contacts Type | mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1 |
Average Impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
Brand | Square D |
Brand, Manufacturer | Schneider Electric |
California Proposition 65 : WARNING: This product can expose you to chemicals including | Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Catalog Number | LC2D18B7 |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Circularity Profile | ENVEOLI1501004 |
Climatic Withstand | IACS E10 || IEC 60947-1 Annex Q category D |
Coil Power Rating | 7.5-7.5 VA 60 HZ 0.3 20 A Degrees C)-7-7 VA 50 HZ 0.3 20 A Degrees C) |
Coil Technology | without built-in suppressor module |
Coil Voltage | 24 Vac |
Coil Volts | 24VAC at 50/60Hz, 24 V AC |
Connection | CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-4 MMA?FLEXIBLE WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-4 MMA?FLEXIBLE WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-4 MMA?FLEXIBLE WITH CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-2.5 MMA?FLEXIBLE WITH CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-4 MMA?SOLID WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-4 MMA?SOLID WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 1 1.5-6 MMA?FLEXIBLE WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 2 1.5-6 MMA?FLEXIBLE WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 1 1-6 MMA?FLEXIBLE WITH CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 2 1-4 MMA?FLEXIBLE WITH CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 1 1.5-6 MMA?SOLID WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 2 1.5-6 MMA?SOLID WITHOUT CABLE END |
Connection Type | Screw Clamp |
Connections - Terminals | control circuit screw clamp terminals 1 1-4 mm?flexible without cable end || control circuit screw clamp terminals 2 1-4 mm?flexible without cable end || control circuit screw clamp terminals 1 1-4 mm?flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm?flexible with cable end || control circuit screw clamp terminals 1 1-4 mm?solid || control circuit screw clamp terminals 2 1-4 mm?solid || power circuit screw clamp terminals 1 1.5-6 mm?flexible without cable end || power circuit screw clamp terminals 2 1.5-6 mm?flexible without cable end || power circuit screw clamp terminals 1 1-6 mm?flexible with cable end || power circuit screw clamp terminals 2 1-4 mm?flexible with cable end || power circuit screw clamp terminals 1 1.5-6 mm?solid || power circuit screw clamp terminals 2 1.5-6 mm?solid |
Contact Configuration | 1NO, 1NC |
Contact Current Rating, Full Load Amps-Inductive | 18 A |
Contact Operation | 3NO |
Contact Rating | 10 A 60 A Degrees C SIGNALLING CIRCUIT-32 A 60 A Degrees C POWER CIRCUIT |
Contactor Application | resistive load || motor control |
Control Circuit Type | AC 50/60 Hz |
Control Circuit Voltage Limits | 0.3...0.6 Uc -40-70 ?C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 ?C operational AC 50 Hz || 0.85...1.1 Uc -40-60 ?C operational AC 60 Hz || 1...1.1 Uc 60-70 ?C operational AC 50/60 Hz |
Control Voltage | 24 V |
Country of Origin | FR - France |
Country of Origin, Country of Origin (subject to change) | France |
Depth | 86 mm |
Device Presentation | preassembled with reversing power busbar |
Device Short Name | LC2D |
ECCN | EAR99 |
Environmental Disclosure | ENVPEP1501004 |
Eu Rohs Directive | Compliant |
Fire Resistance | 850 ?C IEC 60695-2-1 |
Flame Retardance | V1 conforming to UL 94 |
Heat Dissipation | 2-3 W 50/60 Hz |
Height | 77 mm |
Hold-In Power Consumption In Va | 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 ?C) || 7-7 VA 50 Hz cos phi 0.3 (at 20 ?C) |
Inrush Power In Va | 70-70 VA 60 Hz cos phi 0.75 (at 20 ?C) || 70-70 VA 50 Hz cos phi 0.75 (at 20 ?C) |
Insulation Resistance | > 10 MOhm for signalling circuit |
Interlocking Type | mechanical |
Ip Degree Of Protection | IP20 front face IEC 60529 |
Irms Rated Making Capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947 |
Item | IEC Magnetic Contactor |
Item Type | Reversing contactor;LC2D |
Made in USA | No |
Max. Inductive Amps (AC3) | 18A |
Max. Resistive Amps (AC1) | 32A |
Maximum Horse Power Rating | 1 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 5 hp at 230/240 V AC 60 Hz for 3 phase motors || 10 hp at 460/480 V AC 60 Hz for 3 phase motors || 15 hp at 575/600 V AC 60 Hz for 3 phase motors |
Maximum Operating Rate | 3600 cyc/h 60 ?C |
Mechanical Durability | 15 Mcycles |
Mechanical Robustness | vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms |
Mercury Free, Pvc Free, Reach Free Of Svhc, Rohs Exemption Information, Toxic Heavy Metal Free | Yes |
Minimum Switching Current | 5 mA for signalling circuit |
Minimum Switching Voltage | 17 V for signalling circuit |
Motor Power Kw | 4 kW at 220...230 V AC 50-60 Hz || 7.5 kW at 380...400 V AC 50-60 Hz || 9 kW at 415 V AC 50-60 Hz || 9 kW at 440 V AC 50-60 Hz || 10 kW at 500 V AC 50-60 Hz || 10 kW at 660...690 V AC 50-60 Hz |
Mounting | Rail Plate |
Mounting Support | plate || rail |
Mounting Type | DIN Rail Mount ; Panel Mount, Din Rail, Plate, Panel |
Net Weight | 0.707 kg |
Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact |
Number of Poles, Phase, Poles, Pollution Degree | 3 |
Operating Altitude | 0...9842.52 ft (0...3000 m) |
Operating Cycles | 25...400 HZ,3600 CYC/H 60 A Degrees C |
Operating Temperature | -20-60 A Degrees C,-40-70 A Degrees C AT UC |
Operating Time | 12...22 ms closing || 4...19 ms opening |
Overvoltage Category | III |
Pole Contact Composition | 3 NO |
Poles Description | 3P |
Power Dissipation Per Pole | 0.8 W AC-3 || 2.5 W AC-1 || 0.8 W AC-3e |
Product Certifications | DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA |
Product Name, Series | TeSys Deca |
Product Or Component Type | reversing contactor |
Protective Cover | with |
Protective Treatment | TH IEC 60068-2-30 |
Range | TeSys || TeSys Deca |
Rated Breaking Capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Series | TeSys Deca Series |
Series, Sub Brand | TeSys D |
Signalling Circuit Frequency | 25...400 Hz |
Single-Phase HP Rating (Max.) | 3 hp |
Size | 77 MM,86 MM,90 MM |
Special Features | 1 HP 115 V AC 60 HZ 1 PHASE-3 HP 230/240 V AC 60 HZ 1 PHASE-5 HP 200/208 V AC 60 HZ 3 PHASE-5 HP 230/240 V AC 60 HZ 3 PHASE-10 HP 460/480 V AC 60 HZ 3 PHASE-15 HP 575/600 V AC 60 HZ 3 PHASE,WITHOUT BUILT-IN SUPPRESSOR MODULE |
Standard | DNV;CSA;CCC;UL;GL;LROS (Lloyds register of shipping);BV;RINA;GOST;UKCA |
Standards | RoHS, REACh, CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1 |
Sustainable Offer Status | Green Premium product |
Temperature Rating | -40 to 60 ?C |
Tightening Torque | power circuit 1.7 N.m screw clamp terminals flat ? 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat ? 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2 |
Type | IEC Contactor |
UNSPSC | 39121529 |
UPC, UPC Code | 785901207443 |
Utilisation Category | AC-3 || AC-1 || AC-3e |
Voltage | 690VAC, 300VDC |
Warranty | 18 months |
Warranty Description | Contractual Warranty:18 months |
Wattage | 0.8 W AC-3-2.5 W AC-1 |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Width | 90 mm |