Attributes

Key Value
[Ics] Rated Service Sho.100 % 230/240 V AC 50/6.
[Ith] Conventional Free.1 A IEC 60947-4-1
[Ue] Rated Operational .690 V AC 50/60 Hz IEC 6.
[Ui] Rated Insulation V.690 V AC 50/60 Hz IEC 6.
[Uimp] Rated Impulse Wi.6 kV IEC 60947-2
Ambient Air Temperature.-20-60 ?C
Ambient Air Temperature.-40-80 ?C
Breaking Capacity100 kA Icu 230/240 V AC.
California Proposition .Antimony oxide & Antimo.
China Rohs RegulationProduct out of China Ro.
Circularity ProfileENVEOLI2211002
Climatic WithstandIACS E10
Colordark grey
Control Typerotary handle
Depth97 mm
Device Applicationmotor protection
Device Short NameGV2P
Electrical Durability100000 cycles AC-3 415 .
Environmental DisclosureENVPEP2211002
Eu Rohs DirectiveCompliant
Fire Resistance960 ?C IEC 60695-2-11
Fixing Mode35 mm symmetrical DIN r.
Height89 mm
Ik Degree Of ProtectionIK04
Ip Degree Of ProtectionIP20 IEC 60529
Line Rated Current1 A
Magnetic Tripping Curre.13-13 A
Mechanical Durability100000 cycles
Mechanical Robustnessshocks 30 Gn for 11 ms .
Motor Power Kw0.25-0.25 kW 400/415 V .
Network Frequency50/60 Hz IEC 60947-4-1
Network TypeAC
Operating Altitude6561.68 ft (2000 m)
Phase Failure Sensitivi.yes IEC 60947-4-1
Poles Description3P
Power Dissipation Per P.2.5 W
Product CertificationsCCC || UL || CSA || EAC.
Product NameTeSys GV2 || TeSys Deca
Product Or Component Ty.motor circuit breaker
RangeTeSys Deca
Rated Dutycontinuous IEC 60947-4-1
Reach RegulationReference contains Subs.
StandardsEN/IEC 60947-2 || EN/IE.
Suitability For Isolati.yes IEC 60947-1 ? 7-1-6
Thermal Protection Adju.0.63-1 A IEC 60947-4-1
Tightening Torque1.7 N.m screw clamp ter.
Trip Unit Technologythermal-magnetic
Utilisation Categorycategory A IEC 60947-2 .
Warranty18 months
WeeeThe product must be dis.
Width45 mm