Attributes

Key Value
[Icw] Rated Short-Time .260 A 40 ?C - 10 s powe.
[Ith] Conventional Free.10 A 60 ?C signalling c.
[Uc] Control Circuit Vo.24 V AC 50/60 Hz
[Ui] Rated Insulation V.power circuit 690 V IEC.
[Uimp] Rated Impulse Wi.6 kV IEC 60947
Ambient Air Temperature.-40-60 ?C || 60-70 ?C w.
Ambient Air Temperature.-60-80 ?C
Auxiliary Contact Compo.1 NO + 1 NC
Auxiliary Contacts Typemechanically linked 1 N.
Average Impedance2 mOhm - Ith 50 A 50 Hz.
California Proposition .Antimony oxide & Antimo.
China Rohs RegulationPro-active China RoHS d.
Circularity ProfileENVEOLI1102029EN
Climatic WithstandIACS E10 || IEC 60947-1.
Coil Technologywithout built-in suppre.
Connections - Terminalscontrol circuit lugs-ri.
Contactor Applicationmotor control || resist.
Control Circuit TypeAC 50/60 Hz
Control Circuit Voltage.0.3...0.6 Uc -40-70 ?C .
Depth92 mm
Device Short NameLC1D
Environmental DisclosureENVPEP110229EN
Eu Rohs DirectiveCompliant
Fire Resistance850 ?C IEC 60695-2-1
Heat Dissipation2-3 W 50/60 Hz
Height85 mm
Hold-In Power Consumpti.7.5-7.5 VA 60 Hz 0.3 20.
Inrush Power In Va70-70 VA 60 Hz 0.75 20 .
Insulation Resistance> 10 MOhm signalling ci.
Ip Degree Of ProtectionIP20 front face IEC 605.
Irms Rated Making Capac.140 A AC signalling cir.
Maximum Horse Power Rat.2 hp 115 V at AC 50/60 .
Maximum Operating Rate3600 cyc/h 60 ?C
Mechanical Durability15 Mcycles
Mechanical Robustnessvibrations contactor op.
Mercury FreeYes
Minimum Switching Curre.5 mA signalling circuit
Minimum Switching Volta.17 V signalling circuit
Motor Power Kw7.5 kW 220...230 V AC 5.
Mounting Supportrail || plate
Net Weight0.375 kg
Non-Overlap Time1.5 ms on de-energisati.
Operating Altitude0...9842.52 ft (0...300.
Operating Time12...22 ms closing || 4.
Overvoltage CategoryIII
Pole Contact Composition3 NO
Poles Description3P
Pollution Degree3
Power Dissipation Per P.2 W AC-3 || 5 W AC-1 ||.
Product CertificationsBV || CSA || UL || RINA.
Product NameTeSys D || TeSys Deca
Product Or Component Ty.contactor
Protective Coverwith
Protective TreatmentTH IEC 60068-2-30
Pvc FreeYes
RangeTeSys || TeSys Deca
Rated Breaking Capacity550 A 440 V power circu.
Reach Free Of SvhcYes
Reach RegulationFree of Substances of V.
Rohs Exemption Informat.Yes
Safety Reliability LevelB10d = 1369863 cycles c.
Signalling Circuit Freq.25...400 Hz
StandardsCSA C22.2 No 14 || EN 6.
Sustainable Offer StatusGreen Premium product
Tightening Torquecontrol circuit 1.7 N.m.
Toxic Heavy Metal FreeYes
Utilisation CategoryAC-3 || AC-1 || AC-4 ||.
Warranty18 months
WeeeThe product must be dis.
Width45 mm