prev
SQUARE D SQDXMLRM01G1N26
SQUARE Dzoom
brand:
manufacturer:

Attributes

Key ^Value
[Uimp] Rated Impulse Withstand Voltage0.5 kV DC
[Us] Rated Supply Voltage24 V DC SELV 17-33 V)
Adjustable Range Of Switching Point On Falling Pressure-0.97--0.05 bar || -14.1--0.73 psi || -97-5 kPa
Adjustable Range Of Switching Point On Rising Pressure-1--0.08 bar || -14.5--1.16 psi || -100--8 kPa
Ambient Air Temperature For Operation-20-80 ?C
Ambient Air Temperature For Storage-40-80 ?C
Analogue Output Function4...20 mA
California Proposition 65 : WARNING: This product can expose you to chemicals includingDiisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Contacts Type And CompositionNO/NC programmable
Controlled Fluidfresh water 0-80 ?C) || air -20-80 ?C) || hydraulic oil -20-80 ?C) || refrigeration fluid -20-80 ?C)
Depth42 mm
Destruction Pressure, Maximum Permissible Accidental Pressure43 psi || 3 bar || 300 kPa
Device Short NameXMLR
Discrete Output Typesolid state NPN, NO/NC programmable
Display Response Time Typefast 50 ms || normal 200 ms || slow 600 ms
Display Type4 digits 7 segments
Drift Of The Sensitivity+/- 0.03 % of measuring range/?C
Drift Of The Zero Point+/- 0.1 % of measuring range/?C
Electrical Connectionmale connector M12, 4 pins
Electromagnetic Compatibilitysusceptibility to electromagnetic fields 10 V/m 80...2000 MHz EN/IEC 61000-4-3 || immunity to conducted RF disturbances 10 V 0.15...80 MHz EN/IEC 61000-4-6 || surge immunity test 1 kV EN/IEC 61000-4-5 || electrical fast transient/burst immunity test 2 kV EN/IEC 61000-4-4 || electrostatic discharge immunity test 8 kV air, 4 kV contact EN/IEC 61000-4-2
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Fluid Connection Type1/4" - 18 NPT (female)
Front Materialpolyester
Height100 mm
Housing Materialpolyacrylamide || 316L stainless steel
Ip Degree Of ProtectionIP65 conforming to EN/IEC 60529 || IP67 conforming to EN/IEC 60529
Local Signallingfor light ON when switch is actuated 1 LED (yellow)
MarkingCE
Materials In Contact With Fluidceramic || 316L stainless steel || fluorocarbon FKM (Viton)
Maximum Delay First Up300 ms
Maximum Switching Current250 mA
Maximum Voltage Drop2 V
Mechanical Durability10000000 cycles
Mercury Free, Reach Free Of Svhc, Rohs Exemption InformationYes
Minimum Differential Travel0.43 psi || 3 kPa || 0.03 bar
Net Weight0.212 kg
Operating Positionany position, but disposals can falsified the measurement in case of upside down mounting
Pressure Sensor Size-1 bar || -14.5 psi
Pressure Sensor Typepressure transmitter
Pressure Switch Type Of Operationpressure transmitter with 1 switching output
Product CertificationscULus || EAC
Product Or Component Typeelectronic pressure sensors
Protection Typeshort-circuit protection || reverse polarity || overvoltage protection || overload protection
Range Of ProductOsiSense XM
Reach RegulationFree of Substances of Very High Concern above the threshold
Scale Typefixed differential
Shock Resistance50 gn EN/IEC 60068-2-27
StandardsEN/IEC 61326-2-3 || UL 61010-1
Time Delay Range0...50 s in steps of 1 second
Type Of Output Signalanalogue + discrete
Vibration Resistance20 gn 10-2000 Hz)EN/IEC 60068-2-6
Width41 mm