Alarm Contacts | Rear-mounted DB-9 connector sends loss of primary / backup AC |
Ambient Temperature | 32? to 104? F / 0? to 40? C |
Amps | 15A |
Audible Alarm | Buzzer beeps when loss of primary or backup AC occurs |
Audible Alarm On / Off | Enable / Disable switch |
Cord | Optional |
Current Rating | 15 A |
Dimensions: Inches / mm | W: 11.25" / 286 mm H: 3" / 76 mm D: 10" / 254 mm |
Freq. Options | 50/60 Hz |
Frequency Range | 47 to 63 Hz, Caution: Both sources must use same nominal frequency |
Input Type | IEC320 C-14 |
Load Regulation | 1 % from no load to full load |
Output Type | IEC320 C-13 |
Plug Models: -3x02 / -3x03 /-3x04 / -5x02 / -5x03 /-5x04 / -7x02 / -7x03 | 6-15P / L6-15P / IEC 60320 C14 / 6-20P / L6-20P / IEC 60320 C20 / 6-30P / L6-30P |
Power Efficiency | 99 % or higher |
Receptacle Models: -3x02 / -3x03 /-3x04 / -5x02 / -5x03 /-5x04 / -7x02 / -7x03 | 6-15R / L6-15R / IEC 60320 C13 / 6-20R / L6-20R / IEC 60320 C19 / 6-30R / L6-30R |
Safety | UL 60950-1 Issue: 2007/03/27 Ed:2 UL Standard for Safety Information Technology Equipment - Safety - Part 1: General Requirements - CSA C22.2#60950-1 Issued: 2007/03/01 Ed:2 Information Technology Equipment Safety Part 1: General Requirements |
Switching Technology | Mechanical relays |
Transfer Time | Under one cycle |
VA at 220 V | 3600 |
Voltage / Current | 240 V / 15 A |
Voltage Options | 240 V |
Voltage Range | 240 V; 184 - 264 V ? 2.5 % nominal |
Wall or Floor Mount Kit | MK-4000C |
Weight: lbs / kg | 8 lbs / 3.63 kg |