Blade size | 0.6 x 3.5 mm |
Certificate No. (ATEX) | DEMKO15ATEX1346U |
Certificate No. (CSA) | 12400-391 |
Certificate No. (IECEX) | IECEXULD15.0003U |
Certificate No. (UR) | E60693 |
Clamping range, max., Connection cross-section, stranded, max., Wire connection cross section, finely stranded, max., Wire connection cross-section, solid core, max. | 4?mm? |
Clamping range, min. | 0.05?mm? |
Clamping screw | M 2.5 |
Colour | blue |
Conductor size Factory wiring max. (UR), Conductor size Field wiring max. (UR), Wire cross section max. (CSA) | 12 AWG |
Conductor size Factory wiring min. (UR), Conductor size Field wiring min. (UR) | 22 AWG |
Connection cross-section, stranded, min., Wire connection cross section, finely stranded with wire-end ferrules DIN 46228/1, 2 clampable wires, max., Wire cross-section, finely stranded, two clampable wires, max. | 1.5?mm? |
Connection direction | on side |
Continuous operating temp., max. | 120??C |
Continuous operating temp., min. | -50??C |
Current (ATEX), Current (IECEX) | 21 A |
Current at maximum wires | 32?A |
Current size B (UR), Current size C (UR) | 20 A |
Current size C (CSA) | 25 A |
Depth including DIN rail | 63?mm |
eClass 9.0, eClass 9.1 | 27-14-11-20 |
End cover plate required, Explosion-tested version, N-function | Yes |
ETIM 6.0, ETIM 7.0 | EC000897 |
Ex 2014/34/EU label | II 2 G D |
Gauge to IEC 60947-1 | A3 |
Height | 69?mm |
Height (inches) | 2.717?inch |
Levels cross-connected internally, PE connection, PE function, PEN function | No |
Marking EN 60079-7 | Ex eb II C Gb |
Material | Wemid |
Max. voltage (ATEX), Max. voltage (IECEX) | 275 V |
Net weight | 11.81?g |
Number of clamping points per level, Number of levels, Number of potentials | 2 |
Number of connections | 4 |
Number of potentials per tier, Number of similar terminals, Torque level with DMS electric screwdriver | 1 |
Open sides | right |
Operating temperature range | For operating temperature range see EC Design Test Certificate / IEC Ex-Certificate of Conformity |
Pollution severity | 3 |
Power loss in accordance with IEC 60947-7-x | 0.77?W |
Rail | TS 35 |
Rated cross-section, Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max., Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. | 2.5?mm? |
Rated current | 24?A |
Rated impulse withstand voltage | 6 kV |
Rated voltage | 400?V |
Standards | IEC 60947-7-1 |
Storage temperature | 10 ?C...40 ?C |
Storage temperature, max. | 40??C |
Storage temperature, min. | 10??C |
Stripping length | 10?mm |
Tightening torque, max. | 0.6?Nm |
Tightening torque, min. | 0.4?Nm |
TS 35 offset | 35.5?mm |
Type of connection | Screw connection |
Type of mounting | Snap-on |
UL 94 flammability rating | V-0 |
Version | Screw connection, for plug-in cross-connector, One end without connector |
Voltage size B (UR), Voltage size C (CSA), Voltage size C (UR) | 300 V |
Volume resistance according to IEC 60947-7-x | 1.33?m? |
Weight | 9.27?g |
Width | 5.1?mm |
Width (inches) | 0.201?inch |
Wire connection cross section AWG, max. | AWG 12 |
Wire connection cross section AWG, min. | AWG 30 |
Wire connection cross section, finely stranded with wire-end ferrules DIN 46228/1, 2 clampable wires, min., Wire connection cross section, finely stranded, two clampable wires, min., Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min., Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min., Wire connection cross-section, finely stranded, min., Wire connection cross-section, solid core, min. | 0.5?mm? |
Wire cross section max. (ATEX), Wire cross section max. (IECEX) | 4 mm? |
Wire cross section min. (CSA) | 26 AWG |