Attributes

Key Value
[Ue] Rated Operational .480Y/277 V AC
Ambient Air Temperature.40 ?C
Awg GaugeAWG 12...AWG 2/0 alumin.
Breaking Capacity35 kA 277 V AC || 65 kA.
Breaking Capacity CodeG
China Rohs RegulationProduct out of China Ro.
Circuit Breaker Applica.HACR rated
Depth4.05 in
Device Compositionshunt trip
Device Short NameEGB
Electrical Connectionlugs aluminium
Eu Rohs DirectiveCompliant
Height5.66 in
Holding Current1000 A
Line Rated Current80 A
Local Signallingtrip indicator
Mercury FreeYes
Module TypeE-Frame
Mounting Modebolt-on
Net Weight4 lb(US)
Number Of Poles3
Number Of Spaces4
Number Of Spaces Requir.4
Product CertificationscULus
Product DestinationNF panelboard
Product Or Component Ty.miniature circuit-break.
Protection Typeshort-circuit || overlo.
Range Of Product125 A Frame EDB-EGB-EJB
Reach RegulationReference contains Subs.
Rohs Exemption Informat.Yes
Tightening Torque3.9-3.9 N.m 2.5-6 mm? (.
Trip Unit Rating2300-2300 A
Trip Unit Technologythermal-magnetic
Warranty18 months
Width3.92 in