| [Icw] rated short-time withstand current | 25 A = 15 s power circuit, 50 A 55 A 75 A 100 A 105 A 115 A |
| [Ie] rated operational current | 16 A ( 20 A ( |
| [Ith] conventional free air thermal current | 20 A at |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz for power circuit |
| [Ui] rated insulation voltage | 600 V for power circuit conforming to UL 508, 600 V for power circuit conforming to CSA C22.2 No 14, 690 V for power circuit conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Ambient air temperature for operation | -13...122 ?F (-25...50 ?C) |
| Ambient air temperature for storage | -58...176 ?F (-50...80 ?C) |
| Associated fuse rating | 25 A aM for power circuit, 25 A gG at |
| Average impedance | 3 mOhm at 50 Hz - Ith 20 A for power circuit |
| Category | 22326 - CTR,K-LINE,AC,OPEN,NONREV |
| Commercial Status | Commercialised |
| Connections - terminals : Screw clamp terminals 1 cable(s) 0...0 in? (0.34...2.5 mm?) - cable stiffness, Connections - terminals : Screw clamp terminals 2 cable(s) 0...0 in? (0.34...1.5 mm?) - cable stiffness | flexible - with cable end |
| Connections - terminals : Screw clamp terminals 1 cable(s) 0...0.01 in? (0.75...4 mm?) - cable stiffness, Connections - terminals : Screw clamp terminals 2 cable(s) 0...0.01 in? (0.75...4 mm?) - cable stiffness | flexible - without cable end |
| Connections - terminals : Screw clamp terminals 1 cable(s) 0...0.01 in? (1.5...4 mm?) - cable stiffness, Connections - terminals : Screw clamp terminals 2 cable(s) 0...0.01 in? (1.5...4 mm?) - cable stiffness | solid |
| Contactor application | Resistive load |
| Control circuit type | AC 50/60 Hz |
| Control circuit voltage | 480 V AC 50/60 Hz |
| Control circuit voltage limits | 0.2...0.75 Uc at 0.8...1.15 Uc at |
| Country of origin | FR |
| Depth | 2.24 in (57 mm) |
| Device short name | LC1K |
| Discount Schedule | I12 |
| Electrical durability | 0.3 Mcycles 20 A AC-1 at Ue |
| Flame retardance | Requirement 2 conforming to NF F 16-101, Requirement 2 conforming to NF F 16-102, V1 conforming to UL 94 |
| GTIN | 00785901790143 |
| Heat dissipation | 1.3 W |
| Height | 2.28 in (58 mm) |
| Hold-in power consumption in VA | 4.5 VA at 68 ?F (20 ?C) |
| Inrush power in VA | 30 VA at 68 ?F (20 ?C) |
| IP degree of protection | IP2x conforming to VDE 0106 |
| Irms rated making capacity | 144 A AC for power circuit conforming to IEC 60947, 144 A AC for power circuit conforming to NF C 63-110 |
| Mechanical durability | 10 Mcycles |
| Mechanical robustness | Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27, Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27, Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27, Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27, Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27, Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27, Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6, Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6 |
| Mounting support | Plate, Rail |
| Nbr. of units in pkg. | 1 |
| Operating altitude | 6561.68 ft (2000 m) without derating in temperature |
| Operating rate | 3600 cyc/h |
| Operating time | 10...20 ms coil energisation and NO closing, 10...20 ms coil de-energisation and NO opening |
| Overvoltage category | III |
| Package weight(Lbs) | 0.40 |
| Period | 18 months |
| Pole contact composition | 4 NO |
| Poles description | 4P |
| Product availability | Non-Stock - Not normally stocked in distribution facility |
| Product certifications | UL, CSA |
| Product end of life instructions | Need no specific recycling operations |
| Product environmental profile | Available, Download?Product environmental |
| Product or component type | Contactor |
| Product weight | 0.4 lb(US) (0.18 kg) |
| Protective treatment | TC conforming to DIN 50016, TC conforming to IEC 60068 |
| Range of product | TeSys K |
| Rated breaking capacity | 70 A at 660...690 V conforming to IEC 60947, 110 A at 440 V conforming to IEC 60947, 80 A at 500 V conforming to IEC 60947 |
| REACh | Reference not containing SVHC above the threshold |
| Returnability | N |
| RoHS | Schneider Electric declaration of conformity, Compliant - since 0640 - |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Standards | BS 5424, NF C 63-110, IEC 60947, VDE 0660 |
| Sustainable offer status | Green Premium product |
| Tightening torque | 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat ? 6 mm, 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2 |
| Utilisation category | AC-1 |
| Width | 1.77 in (45 mm) |