Key Value
[Ics] Rated Service Bre.35 kA 240 V AC 50/60 Hz.
[Ue] Rated Operational .600 V AC 50/60 Hz UL 489
[Ui] Rated Insulation V.750 V IEC 60947-2
[Uimp] Rated Impulse Wi.8 kV IEC 60947-2
Ambient Air Temperature.-25-70 ?C
Ambient Air Temperature.-50-85 ?C
Awg GaugeAWG 3/0...750 kcmil alu.
Breaking CapacityAIR 100 kA 240 V AC 50/.
Breaking Capacity CodeJ
California Proposition .DINP, which is known to.
China Rohs RegulationProduct out of China Ro.
Circularity ProfileENVEOLI1407013EN
Continuous Current Rati.80 %
Control Typeoperating handle
Depth14.49 in
Device Applicationdistribution
Electrical Connectionbusbar connection line .
Environmental DisclosureENVPEP1407013EN
Eu Rohs DirectiveCompliant
Halogen Content Perform.Halogen free plastic pa.
Height16.24 in
Ip Degree Of ProtectionIP40
Line Rated Current600-600 A
Local Signallingalarm 1 LED yellow)long.
Mercury FreeYes
Mounting Modeunit mount busbar)
Mounting Supportbusbar
Net Weight52 lb(US)
Network Frequency50/60 Hz
Number Of Slots2 auxiliary switch OF p.
Poles Description3P
Pollution Degree3 IEC 60947-1
Product CertificationsUL || CSA || NOM
Product NamePowerPact R
Product Or Component Ty.circuit breaker
Pvc FreeYes
Quality LabelsCE
Quantity Per Set1
RangePowerPact
Reach RegulationReference contains Subs.
Rohs Exemption Informat.Yes
StandardsUL || CSA || NEMA || NM.
Suitability For Isolati.yes IEC 60947-2
Sustainable Offer StatusGreen Premium product
Terminal IdentifierAL2500RK
Tightening Torque62-62 N.m 50-400 mm? (A.
Trip Unit NameMicrologic 5.0
Trip Unit Technologyelectronic, standard, M.
Utilisation Categorycategory A
Warranty18 months
Width16.53 in
Wire Stripping Length35 mm