[Ue] Rated Operational Voltage | 24 V DC |
Ambient Air Temperature For Operation | -10-60 ?C |
Ambient Air Temperature For Storage | -25-85 ?C |
Analogue Input Number | 4 |
Analogue Input Resolution | 16 bits |
Analogue Input Type | KTY 84 silicon temperature probe || KTY 10 silicon temperature probe || Pt 1000 temperature probe || Pt 100 temperature probe |
Bus Type | TM7 bus |
California Proposition 65 : WARNING: This product can expose you to chemicals including | Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI1409005EN |
Disturbance Radiated/Conducted | CISPR 11 |
Electrical Connection | 1 male connector M12 - B coding - 4 ways bus IN || 1 female connector M12 - B coding - 4 ways bus OUT || 4 female connectors M12 - A coding - 5 ways sensor || 1 male connector M8 - 4 ways power IN || 1 female connector M8 - 4 ways power OUT |
Electromagnetic Compatibility | EN/IEC 61000-4-6 |
Enclosure Material | Plastic |
Environmental Disclosure | ENVPEP1409005EN |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Fixing Mode | by 2 screws |
Input Impedance | 0...3276 Ohm |
Input/Output Number | 4 |
Input/Output Number Of Splitter Box | 4 I |
Ip Degree Of Protection | IP67 conforming to IEC 61131-2 |
Local Signalling | for bus diagnostic 2 LEDs || for sensor/actuator power supply status 2 LEDs |
Marking | CE |
Mercury Free | Yes |
Net Weight | 0.2 kg |
Operating Altitude | 0...6561.68 ft (0...2000 m) |
Operating Position | any position |
Pollution Degree | 2 IEC 60664 |
Product Certifications | GOST-R || ATEX II 3g EEx nA II T5 || cURus || C-tick |
Product Or Component Type | analog I/O expansion block |
Pvc Free | Yes |
Range Compatibility | Modicon M258 || Modicon LMC058 |
Range Of Product | Modicon TM7 |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
Relative Humidity | 5-95 % without condensation or dripping water |
Resistance To Electromagnetic Fields | 10 V/m 0.08-2 Hz EN/IEC 61000-4-3 || 1 V/m 2-2.7 Hz EN/IEC 61000-4-3 |
Resistance To Electrostatic Discharge | 6 kV in contact EN/IEC 61000-4-2 || 8 kV in air EN/IEC 61000-4-2 |
Resistance To Fast Transients | 2 kV EN/IEC 61000-4-4 power supply) || 1 kV EN/IEC 61000-4-4 input/output) || 1 kV EN/IEC 61000-4-4 shielded cable) |
Rohs Exemption Information | Yes |
Sensor Power Supply | 24-24 V overload, short-circuit and reverse polarity protection |
Shock Resistance | 30 gn 11 ms IEC 60721-3-5 Class 5M3 |
Standards | IEC 61131-2 |
Storage Altitude | 0-3000 m |
Surge Withstand | 1 kV power supply (common mode) EN/IEC 61000-4-5 || 0.5 kV power supply (differential mode) EN/IEC 61000-4-5 || 1 kV unshielded links (common mode) EN/IEC 61000-4-5 || 0.5 kV unshielded links (differential mode) EN/IEC 61000-4-5 || 1 kV shielded links (common mode) EN/IEC 61000-4-5 || 0.5 kV shielded links (differential mode) EN/IEC 61000-4-5 |
Sustainable Offer Status | Green Premium product |
Toxic Heavy Metal Free | Yes |
Vibration Resistance | 7.5 mm constant amplitude 2-8 Hz)IEC 60721-3-5 Class 5M3 || 2 gn constant acceleration 8-200 Hz)IEC 60721-3-5 Class 5M3 || 4 gn constant acceleration 200-500 Hz)IEC 60721-3-5 Class 5M3 |
Warranty | 18 months |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |