Mersen STXT480Y10A
Mersenzoom
brand:
manufacturer:

Attributes

Key ^Value
Amps, Lightning Impulse Current, Max. Surge Current per Phase100 kA
Basic MaterialNonmetallic
Chase Nipple Size3/4 in
ColorGray
Country of Origin (subject to change)Mexico
Depth4.0 in
Enclosure MaterialPolycarbonate
Enclosure NEMA Rating4X
FilteringYes
Filtering / NonfilteringFiltering
IncludesEMI/RFI Filter for Cleaner Attenuation
IP Rating65
ItemSurge Protection Device
Length, Length (Straight Wireway)7.4 in
Max. Continuing Operating Voltage320V AC
Max. Operating Temp.185 Degrees F
Max. Surge Current Per Mode50kA
Max. Surge Current per Mode, Max. Surge Current Per Phase100kA
Min. Operating Temp.-40 Degrees F
Modes of ProtectionL-G, L-L, L-N, N-G
ModularNo
Modular / NonmodularNonmodular
Mounting StyleScrew
Noise Attenuation-50db @ 10kHz to 100MHz
Nominal Discharge Current20 kA
Number of Poles3
Number of Wires4 Wires
PhaseThree
Short Circuit Current Rating200kA
StandardsANSI/IEEE C62.41.1, ANSI/UL 1449 4th Edition, C62.41.2, C62.45, CSA C22.2, File E210793, RoHS Compliant, Type 1 SPD, UL96A Lightning Protection
System ConnectionParallel
UL SPD TypeType 1
Voltage277/480V AC Wye
Voltage Protection Rating1200V (L-G, L-N, N-G), 2000V (L-L)
Width7.08 in
Wire Gauge8 AWG