[Ics] Rated Service Breaking Capacity | 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2 |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz IEC 60947-3 |
[Ui] Rated Insulation Voltage | 750 V IEC 60947-2 |
[Uimp] Rated Impulse Withstand Voltage | 8 kV IEC 60947-2 |
AC Voltage Rating | 690V AC |
Actuator Type, Circuit Breaker Actuator, Control Type | toggle |
Ambient Air Temperature For Operation | -2-70 ?C |
Ambient Air Temperature For Storage | -50-85 ?C |
Amps, Current Rating | 90 A |
Application | HACR rated Applications; Distribution |
Awg Gauge, AWG Range | AWG 14...AWG 3/0 aluminium/copper terminal |
Brand | Square D by Schneider Electric |
Breaking Capacity | 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC |
Breaking Capacity Code | D |
California Proposition 65 : WARNING: This product can expose you to chemicals including | DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Catalog Number | HDL26090 |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Circuit Breaker Application | HACR rated |
Circuit Breaker Mounting Style | Unit Mount Lug |
Circularity Profile | ENVEOLI2206027EN |
Color, Color Family | Black |
Communication Interface | Modbus || Ethernet |
Continuous Current Rating | 80 % |
Country of Origin | United States, US - United States |
Current Rating | 90-90A |
Depth | 86 mm |
Device Application | distribution |
Dimensions | 6.4 H x 4.12 W x 4.36 D in |
Display | HDL26090 Circuit Circuit Breaker, PowerPact H, 90A, 2 Pole, 600VAC, 14kA, lugs, thermal magnetic, 80% |
ECCN | EAR99 |
Electrical Connection | lugs line || lugs load |
Environmental Disclosure | ENVPEP2206027EN |
Eu Rohs Directive | Compliant |
Family Name | PowerPact H Family |
Features | Mercury Free; PVC Free |
Frame Size | H |
Frame Type | H Frame |
Height | 163 mm |
High Amp Trip Setting | 1450 A |
Interrupt Rating | 14kA, 25kA@240VAC ; 18kA@480VAC ; 14kA@600VAC, 25 kA at 220/240V AC, 18 kA at 380/440/415/480V AC, 14 kA at 500/525/600V AC, 20 kA at 250/500V DC |
Ip Degree Of Protection | front cover IP40 IEC 60529 |
Item | Circuit Brkr,PowerPact H,thermal magne |
Length, Wire Stripping Length | 16 mm |
Line Rated Current | 90-90 A |
Local Signalling | switched off (OFF) 1 trip indicator green) |
Made in USA, Mercury Free, Pvc Free, Rohs Exemption Information | Yes |
Magnetic Hold Current | 800 A |
Magnetic Tripping Current | 1450-1450 A |
Manufacturer | Schneider Electric |
Max. AIR Rating | 25 kA |
Max. Wire Size | 3/0 AWG (Cu/Al) |
Min. Wire Size | 14 AWG (Cu/Al) |
Mounting Mode | unit mount lug) |
Mounting Support, Terminal Connection | Lug |
Mounting Type | Panel Mount |
Net Weight | 2.2 kg |
Network Frequency | 50/60 Hz |
No. of Poles | 2-Pole |
Number of Poles | 2 |
Number Of Slots | 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in) |
Poles Description | 2P |
Pollution Degree | 3 IEC 60947-1 |
Product Certifications | UL || CSA || NOM |
Product Name | PowerPact H |
Product Or Component Type | circuit breaker |
Protected Poles Description | 2t |
Quality Labels | CE |
Quantity Per Set | 1 |
Range | PowerPact |
Rated Voltage | 690V AC 50/60 Hz IEC 60947-3 |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
Series | PowerPact H-Frame Series |
Standard, Standards | UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2 |
Standards | UL, CSA, NEMA, NOM, CE, UL 489 ; IEC/EN 60947-2 ; CSA C22.2 No. 5 ; Federal Specification W-C-375B/GEN ; NEMA AB1 ; NMX J-266 ; CCC ; CE Marked |
Suitability For Isolation | yes IEC 60947-2 |
Sustainable Offer Status | Green Premium product |
Terminal Identifier | AL150HD |
Terminal Type | Line: Lug - Load: Lug |
Termination | Screw |
Tightening Torque, Torque | 5-5 N.m 2.5-6 mm? (AWG 14...AWG 10) || 14-14 N.m 10-95 mm? (AWG 8...AWG 3/0) |
Trip Time | Adjustable Trip |
Trip Type | Thermal Magnetic |
Trip Unit Technology | thermal-magnetic |
Type | Thermal/Magnetic |
UNSPSC | 39121616 |
UPC, UPC Code | 785901625193 |
Utilisation Category | category A |
Voltage Rating | 600 V |
Warranty | 18 months |
Warranty Description | Contractual Warranty:18 months |
Weight | 5.00 lbs. |
Width | 104 mm |
Wire Size | 3/0-14 AWG |