Attributes

Key Value
[Ie] Rated Operational .power circuit 40 A AC A.
[Ith] Conventional Free.10 A 60 ?C control circ.
[Uc] Control Circuit Vo.120 V AC 50/60 Hz
[Ui] Rated Insulation V.control circuit 600 V C.
[Uimp] Rated Impulse Wi.6 kV IEC 60947
Ambient Air Temperature.-5-60 ?C
Ambient Air Temperature.-60-80 ?C
Assembly Styleready assembled
Auxiliary Contact Compo.1 NO + 1 NC
Auxiliary Contacts Typemechanically linked 1 N.
Average ImpedanceIth 60 A 50 Hz power ci.
California Proposition .Antimony oxide & Antimo.
China Rohs RegulationPro-active China RoHS d.
Circularity ProfileENVEOLI1503009EN
Coil Technologywithout built-in bidire.
Coil Typestandard
Connections - Terminalscontrol circuit 1 1-4 m.
Contactor Applicationmotor control
Control Circuit TypeAC
Control Circuit Voltage.drop-out 0.3...0.6 Uc 5.
Depth142 mm
Device Short NameLC2D
Environmental DisclosureENVPEP1503009EN
Eu Rohs DirectiveCompliant
Fire Resistance850 ?C IEC 60695-2-1
Flame RetardanceV1 conforming to UL 94
Heat Dissipation6-10 W 50/60 Hz control.
Height132 mm
Hold-In Power Consumpti.20-20 VA 50 Hz 0.3 20 ?.
Inrush Power In Va200-200 VA 0.75 20 ?C) .
Insulation Resistance> 10 MOhm control circu.
Interlocking Typemechanical
Ip Degree Of ProtectionIP2x IEC 60529 || IP2x .
Irms Rated Making Capac.140 A AC control circui.
Maximum Operating Rate3600 cyc/h 60 ?C
Mechanical Durability6000000 cycles
Mercury FreeYes
Minimum Switching Curre.5 mA control circuit
Minimum Switching Volta.17 V control circuit
Motor Power Kw11 kW 220...240 V AC 50.
Mounting Supportrail || plate
Net Weight2.4 kg
Non-Overlap Time1.5 ms on de-energisati.
Operating Altitude9842.52 ft (3000 m) wit.
Operating Time12...26 ms closing || 4.
Overvoltage CategoryIII
Permissible Ambient Air.-40-70 ?C at Uc
Pole Contact Composition3 NO
Poles Description3P
Power Dissipation Per P.2.4 W AC-3 - Ith 60 A
Product CertificationsGOST || CCC || GL || LR.
Product Or Component Ty.reversing contactor
Protective Coverwith
Protective TreatmentTH 3)IEC 60068
Pvc FreeYes
Range Of ProductTeSys D
Rated Breaking Capacity800 A 440 V power circu.
Reach Free Of SvhcYes
Reach RegulationFree of Substances of V.
Rohs Exemption Informat.Yes
Safety Reliability LevelB10d = 1369863 cycles c.
Shock Resistance10 gn contactor closed .
StandardsCSA C22.2 No 14 || IEC .
Sustainable Offer StatusGreen Premium product
Tightening Torquecontrol circuit 1.7 N.m.
Toxic Heavy Metal FreeYes
Utilisation CategoryAC-4 || AC-2 || AC-3
Vibration Resistance2 gn 5-300 Hz contactor.
Warranty18 months
WeeeThe product must be dis.
Width165 mm