[Ue] Rated Operational Voltage | 120/240 V AC || 240 V AC || 120 V AC || 48 V DC |
Ambient Air Temperature For Operation | 40 ?C |
Awg Gauge | AWG 8...AWG 2 copper or aluminium |
Breaking Capacity | 10 kA 120/240 V AC 50/60 Hz || 10 kA 240 V AC 50/60 Hz || 10 kA 120 V AC 50/60 Hz || 5 kA 48 V DC |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Circuit Breaker Application | HACR rated |
Circuit Breaker Type | standard |
Depth | 74 mm |
Electrical Connection | box lugs |
Eu Rohs Directive | Compliant |
Halogen Content Performance | Halogen free product |
Height | 79 mm |
Line Rated Current | 45 A |
Mercury Free, Rohs Exemption Information | Yes |
Mounting Mode | plug-in |
Net Weight | 0.376 kg |
Number Of Spaces Required | 3 |
Poles Description | 3P |
Product Certifications | UL Listed || CSA |
Product Or Component Type | miniature circuit-breaker |
Range Of Product | QO |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
Tightening Torque | 5-5 N.m 10-25 mm? (AWG 8...AWG 2) |
Type Of Packing | consumer packaging |
Width | 57 mm |