[Us] Rated Supply Voltage | 90...277 V AC 50/60 Hz +/- 1 % |
Ambient Air Temperature For Storage | -40-70 ?C |
Analogue Input Type | 42 solid core CT 100 A |
California Proposition 65 : WARNING | Cancer and Reproductive Harm - www.P65Warnings.ca.gov |
China Rohs Regulation | X |
Communication Of Data | high current alarm || low-low current alarm || low current alarm || high-high current alarm |
Communication Port Protocol | Modbus RTU |
Communication Port Support | RS485 |
Connection Pitch | 26 mm |
Device Application | sub billing |
Device Short Name | BCPMC |
Energy Management | sub billing and cost allocation |
Eu Rohs Directive | Compliant |
Height | 146 mm |
Measurement Accuracy | current 2 % 0.25?2 A || current 1 % 2?100 A |
Measurement Voltage | 90-277 V phase to neutral || 150-480 V phase to phase |
Mercury Free, Rohs Exemption Information | Yes |
Mounting Mode | panel-mounted |
Mounting Support | enclosure || panel |
Net Weight | 1.5 kg |
Network Frequency | 50 Hz || 60 Hz |
Operating Altitude | 9842.52 ft (3000 m) |
Power Monitoring | basic instrumentation |
Product Certifications | UL |
Product Name | PowerLogic BCPM |
Product Or Component Type | multi-circuit energy meter |
Provided Equipment | 42 x current transformer || 2 x cables |
Range | PowerLogic |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
Relative Humidity | 0-95 % 0-60 ?C |
Sampling Rate | 256 samples/cycle |
Standards | ANSI C12.1 || UL 508 || EN 61010 || IEC 61036 |
Type Of Measurement | current |
Update Time | 1.8 s |
Variant | basic |
Warranty | 18 months |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Width | 288 mm |