Attributes

Key Value
9 Mm Pitches6
[Ics] Rated Service Bre.25 kA 220...240 V AC 50.
[Ue] Rated Operational .525 V AC 50/60 Hz UL 489
[Ui] Rated Insulation V.800 V IEC 60947-2
[Uimp] Rated Impulse Wi.8 kV IEC 60947-2
Ambient Air Temperature.-25-70 ?C
Ambient Air Temperature.-50-85 ?C
Awg GaugeAWG 14...AWG 2/0 alumin.
Breaking Capacity25 kA 208Y/120 V AC 50/.
Breaking Capacity CodeD
California Proposition .DINP, which is known to.
China Rohs RegulationProduct out of China Ro.
ColorGray RAL 7016)
Connection Pitch27 mm
Continuous Current Rati.80 %
Control Typetoggle
Depth89 mm
Device Applicationdistribution
Device Short NameBD 035
Electrical ConnectionI-Line connection line .
Electrical Durability10000 cycles IEC 947-1 .
Environmental DisclosureENVPEP1610005EN
Eu Rohs DirectiveCompliant
Halogen Content Perform.Halogen free product
Height137 mm
Ik Degree Of ProtectionIK07 IEC 62262
Ip Degree Of Protectionfront cover IP40 IEC 60.
Line Rated Current35-35 A
Local Signallingpresence of auxiliary c.
Mechanical Durability20000 cycles IEC 947-1 .
Mercury FreeYes
Mounting Height76.2 mm
Mounting ModeI-Line
Net Weight0.952 kg
Network Frequency50/60 Hz
Number Of Slots1 auxiliary switch OF p.
Phase ConnectionAC
Poles Description2P
Pollution Degree3 IEC 60947-1
Product CertificationsUL || IEC || CCC || EAC.
Product NamePowerPact B
Product Or Component Ty.circuit breaker
Pvc FreeYes
Quality LabelsCE
Quantity Per Setset of 1
RangePowerPact
Reach RegulationReference contains Subs.
Rohs Exemption Informat.Yes
StandardsEN/IEC 60947-2 || UL 48.
Suitability For Isolati.yes IEC 60947-2
Sustainable Offer StatusGreen Premium product
Tightening Torque3.6-4.4 N.m 2.5-6 mm? (.
Trip Unit Technologythermal-magnetic
Utilisation Categorycategory A
Width54 mm
Wire Stripping Length20 mm