[Ith] Conventional Free Air Thermal Current | 10 A 60 ?C |
[Ue] Rated Operational Voltage | 690 V AC 25...400 Hz |
[Ui] Rated Insulation Voltage | 690 V IEC 60947-5-1 || 600 V UL || 600 V CSA |
Ambient Air Temperature For Operation | -5-60 ?C |
Ambient Air Temperature For Storage | -60-80 ?C |
Associated Fuse Rating | 10 A gG |
Auxiliary Contact Composition | 1 NO + 1 NC |
Auxiliary Contacts Operation | instantaneous |
California Proposition 65 : WARNING: This product can expose you to chemicals including | Nickel (Metallic), which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Connections - Terminals | screw clamp terminals1 1-2.5 mm? - rigid || screw clamp terminals2 1-2.5 mm? - rigid || screw clamp terminals1 1-2.5 mm? - flexible with or without cable end || screw clamp terminals2 1-2.5 mm? - flexible with or without cable end || screw clamp terminals AWG 10...AWG 18) |
Device Short Name | DPEAN |
Environmental Characteristic | normal environment |
Environmental Disclosure | ENVPEP110807EN_V2 |
Eu Rohs Directive | Compliant |
Insulation Resistance | > 10 MOhm |
Ip Degree Of Protection | IP20 conforming to VDE 0106 |
Irms Rated Making Capacity | 140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1 |
Mechanical Durability | 30 Mcycles |
Mercury Free, Reach Free Of Svhc, Rohs Exemption Information, Toxic Heavy Metal Free | Yes |
Minimum Switching Current | 5 mA |
Minimum Switching Voltage | 17 V |
Mounting Location | front |
Non-Overlap Time | 1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact |
Operating Altitude | 9842.52 ft (3000 m) |
Permissible Ambient Air Temperature Around The Device | -40-70 ?C at Uc |
Permissible Short-Time Rating | 100 A 60 ?C 1 s || 120 A 60 ?C 500 ms || 140 A 60 ?C 100 ms |
Product Certifications | UL || CSA |
Product Or Component Type | auxiliary contact block |
Protective Treatment | TH IEC 60068 |
Range | Easy TeSys |
Range Compatibility | Easy TeSys DPE contactor |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
Standards | IEC 60947-5-1 || EN 60947-5-1 || UL 60947-5-1 |
Sustainable Offer Status | Green Premium product |
Tightening Torque | 1.2 N.m Philips No 2 || 1.2 N.m flat ? 6 mm |