[Ith] Conventional Free Air Thermal Current | 20 A 50 ?C power circuit || 10 A 50 ?C signalling circuit |
[Ui] Rated Insulation Voltage | power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-5-1 || signalling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || signalling circuit 600 V CSA C22.2 No 14 |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Ambient Air Temperature For Operation | -25-50 ?C |
Ambient Air Temperature For Storage | -50-80 ?C |
Auxiliary Contact Composition | 1 NC |
Auxiliary Contacts Type | instantaneous 1 NC |
Average Impedance | 3 mOhm - Ith 20 A 50 Hz power circuit |
California Proposition 65 : WARNING: This product can expose you to chemicals including | Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Circularity Profile | ENVEOLI1503003EN |
Contactor Application | motor control |
Control Circuit Voltage Limits | operational 0.8...1.15 Uc 50 ?C) || drop-out 0.1...0.75 Uc 50 ?C) |
Depth | 57 mm |
Device Short Name | LP1K |
Environmental Disclosure | ENVPEP1503003EN |
Eu Rohs Directive | Compliant |
Flame Retardance | V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102 |
Height | 58 mm |
Hold-In Power Consumption In W | 3-3 W 20 ?C |
Inrush Power In W | 3-3 W 20 ?C) |
Insulation Resistance | > 10 MOhm signalling circuit |
Irms Rated Making Capacity | 110 A AC power circuit NF C 63-110 || 110 A AC power circuit IEC 60947 || 110 A AC signalling circuit IEC 60947 |
Maximum Operating Rate | 3600 cyc/h |
Mechanical Durability | 10 Mcycles |
Mercury Free, Reach Free Of Svhc, Rohs Exemption Information, Toxic Heavy Metal Free | Yes |
Minimum Switching Current | 5 mA signalling circuit |
Minimum Switching Voltage | 17 V signalling circuit |
Mounting Support | plate || rail |
Net Weight | 0.225 kg |
Operating Altitude | 6561.68 ft (2000 m) without derating |
Operating Time | 30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening |
Overvoltage Category | III |
Pole Contact Composition | 3 NO |
Poles Description | 3P |
Product Certifications | UL || CSA || UKCA |
Product Or Component Type | contactor |
Range | TeSys |
Range Of Product | TeSys K |
Rated Breaking Capacity | 110 A 415 V IEC 60947 || 110 A 440 V IEC 60947 || 80 A 500 V IEC 60947 || 110 A 220...230 V IEC 60947 || 110 A 380...400 V IEC 60947 || 70 A 660...690 V IEC 60947 |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Sustainable Offer Status | Green Premium product |
Tightening Torque | 1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat ? 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2 |
Utilisation Category | AC-4 || AC-3 |
Warranty | 18 months |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Width | 45 mm |