prev
SQUARE D SQDLP1K0601FD
SQUARE Dzoom
brand:
manufacturer:

Attributes

Key ^Value
[Ith] Conventional Free Air Thermal Current20 A 50 ?C power circuit || 10 A 50 ?C signalling circuit
[Ui] Rated Insulation Voltagepower circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-5-1 || signalling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || signalling circuit 600 V CSA C22.2 No 14
[Uimp] Rated Impulse Withstand Voltage8 kV
Ambient Air Temperature For Operation-25-50 ?C
Ambient Air Temperature For Storage-50-80 ?C
Auxiliary Contact Composition1 NC
Auxiliary Contacts Typeinstantaneous 1 NC
Average Impedance3 mOhm - Ith 20 A 50 Hz power circuit
California Proposition 65 : WARNING: This product can expose you to chemicals includingAntimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1503003EN
Contactor Applicationmotor control
Control Circuit Voltage Limitsoperational 0.8...1.15 Uc 50 ?C) || drop-out 0.1...0.75 Uc 50 ?C)
Depth57 mm
Device Short NameLP1K
Environmental DisclosureENVPEP1503003EN
Eu Rohs DirectiveCompliant
Flame RetardanceV1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Height58 mm
Hold-In Power Consumption In W3-3 W 20 ?C
Inrush Power In W3-3 W 20 ?C)
Insulation Resistance> 10 MOhm signalling circuit
Irms Rated Making Capacity110 A AC power circuit NF C 63-110 || 110 A AC power circuit IEC 60947 || 110 A AC signalling circuit IEC 60947
Maximum Operating Rate3600 cyc/h
Mechanical Durability10 Mcycles
Mercury Free, Reach Free Of Svhc, Rohs Exemption Information, Toxic Heavy Metal FreeYes
Minimum Switching Current5 mA signalling circuit
Minimum Switching Voltage17 V signalling circuit
Mounting Supportplate || rail
Net Weight0.225 kg
Operating Altitude6561.68 ft (2000 m) without derating
Operating Time30...40 ms coil energisation and NO closing || 10 ms coil de-energisation and NO opening
Overvoltage CategoryIII
Pole Contact Composition3 NO
Poles Description3P
Product CertificationsUL || CSA || UKCA
Product Or Component Typecontactor
RangeTeSys
Range Of ProductTeSys K
Rated Breaking Capacity110 A 415 V IEC 60947 || 110 A 440 V IEC 60947 || 80 A 500 V IEC 60947 || 110 A 220...230 V IEC 60947 || 110 A 380...400 V IEC 60947 || 70 A 660...690 V IEC 60947
Reach RegulationFree of Substances of Very High Concern above the threshold
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Sustainable Offer StatusGreen Premium product
Tightening Torque1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat ? 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
Utilisation CategoryAC-4 || AC-3
Warranty18 months
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Width45 mm