mpn
SQDLUCA1XES
brand
name: SQUARE D
manufacturer
name: SQUARE D
Attributes
Key
Value
[Uc] Control Circuit Vo.
48 V AC || 48...72 V DC
[Ue] Rated Operational .
690 V AC
[Ui] Rated Insulation V.
690 V IEC 60947-6-2 || .
[Uimp] Rated Impulse Wi.
6 kV IEC 60947-6-2
Ambient Air Temperature.
-25-70 ?C
Ambient Air Temperature.
-40-85 ?C
China Rohs Regulation
Product out of China Ro.
Circularity Profile
ENVEOLI100414
Compatibility Code
LUCA
Control Circuit Voltage.
38.5...72 V AC 48 V in .
Depth
60 mm
Device Application
motor control || motor .
Device Short Name
LUCA
Environmental Disclosure
ENVPEP080204EN
Eu Rohs Directive
Compliant
Fire Resistance
960 ?C parts supporting.
Fixing Mode
plug-in front face)
Function Available
protection against phas.
Halogen Content Perform.
Halogen free plastic pa.
Heat Dissipation
2-2 W control circuit w.
Height
66 mm
Immunity To Microbreaks
3 ms
Immunity To Radioelectr.
10 V IEC 61000-4-6
Immunity To Voltage Dips
70 % / 500 ms IEC 61000.
Ip Degree Of Protection
IP20 front panel and wi.
Load Type
3-phase motor self-cool.
Mercury Free
yes
Motor Power Kw
0.25 kW 400...440 V AC .
Net Weight
0.135 kg
Network Frequency
40...60 Hz
Non-Dissipating Shock W.
1 kV serial mode IEC 60.
Operating Altitude
6561.68 ft (2000 m)
Operating Time
35 ms opening with LUB1.
Phase Failure Sensitivi.
yes
Product Certifications
CE || UL || CSA || CCC .
Product Compatibility
power base LUB12 || pow.
Product Name
TeSys Ultra
Product Or Component Ty.
standard control unit
Product Specific Applic.
overload and short-circ.
Protective Treatment
TH IEC 60068
Pvc Free
yes
Range
TeSys
Range Of Product
TeSys Ultra
Reach Regulation
Reference contains Subs.
Resistance To Electrost.
8 kV 3 in open air IEC .
Resistance To Fast Tran.
2 kV 3 serial link IEC .
Resistance To Radiated .
10 V/m 3 IEC 61000-4-3
Rohs Exemption Informat.
yes
Safe Separation Of Circ.
400 V SELV between the .
Shock Resistance
10 gn power poles open .
Standards
EN 60947-6-2 || IEC 609.
Sustainable Offer Status
Green Premium product
Thermal Overload Class
class 10 40-60 Hz -25-7.
Thermal Protection Adju.
0.35-1.4 A
Tripping Threshold
14.2 x Ir +/- 20 %
Typical Current Consump.
280 mA 48 V AC I maximu.
Utilisation Category
AC-41 || AC-43 || AC-44
Vibration Resistance
2 gn 5-300 Hz power pol.
Warranty
18 months
Weee
The product must be dis.
Width
45 mm