Attributes

Key Value
[Ics] Rated Service Bre.35 kA 240 V AC 50/60 Hz.
[Ue] Rated Operational .600 V AC 50/60 Hz UL 489
[Ui] Rated Insulation V.750 V IEC 60947-2
[Uimp] Rated Impulse Wi.8 kV IEC 60947-2
Accessory / Separate Pa.Modbus connecting cable
Ambient Air Temperature.-2-70 ?C
Ambient Air Temperature.-50-85 ?C
Awg Gauge3 x AWG 3/0...3 x 500 k.
Breaking CapacityAIR 100 kA 240 V AC 50/.
Breaking Capacity CodeJ
California Proposition .DINP, which is known to.
China Rohs RegulationProduct out of China Ro.
Circularity ProfileENVEOLI1407012EN
Communication InterfaceModbus
Continuous Current Rati.100 %
Control Typetoggle
Depth8.05 in
Device Applicationdistribution
Electrical ConnectionI-Line connection line .
Environmental DisclosureENVPEP1407012EN
Eu Rohs DirectiveCompliant
Height12.86 in
Ip Degree Of Protectionfront cover IP40
Line Rated Current800-800 A
Local Signallingoverload 1 1 LED amber).
Long Time Pick-Up Adjus.0.4...1 x Ir
Mercury FreeYes
Mounting Height9 in
Mounting ModeI-Line bracket)
Mounting Supportbracket
Net Weight32 lb(US)
Network Frequency50/60 Hz
Number Of Slots2 auxiliary switch OF p.
Phase ConnectionABC
Poles Description3P
Pollution Degree3 IEC 60947-1
Product CertificationsUL || CSA || NOM
Product NamePowerPact P
Product Or Component Ty.circuit breaker
Pvc FreeYes
Quality LabelsCE
Quantity Per Set1
RangePowerPact
Reach RegulationReference contains Subs.
Rohs Exemption Informat.Yes
StandardsUL || CSA || NEMA || NO.
Sustainable Offer StatusGreen Premium product
Terminal IdentifierAL800M23K
Tightening Torque50-50 N.m 95-240 mm? (3.
Trip Unit NameMicrologic 6.0 H
Trip Unit Technologyelectronic, harmonic, M.
Warranty18 months
WeeeThe product must be dis.
Width8.27 in
Wire Stripping Length25 mm