[Ics] Rated Service Breaking Capacity | 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2 |
[Ue] Rated Operational Voltage | 600 V AC 50/60 Hz UL 489 |
[Ui] Rated Insulation Voltage | 750 V IEC 60947-2 |
[Uimp] Rated Impulse Withstand Voltage | 8 kV IEC 60947-2 |
Ambient Air Temperature For Operation | -2-70 ?C |
Ambient Air Temperature For Storage | -50-85 ?C |
Awg Gauge | 3 x AWG 3/0...3 x 500 kcmil aluminium/copper |
Breaking Capacity | AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2 |
Breaking Capacity Code | J |
California Proposition 65 : WARNING: This product can expose you to chemicals including | DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Circularity Profile | ENVEOLI1407012EN |
Continuous Current Rating | 100 % |
Control Type | toggle |
Depth | 8.05 in |
Device Application | distribution |
Electrical Connection | lugs line || lugs load |
Environmental Disclosure | ENVPEP1407012EN |
Eu Rohs Directive | Compliant |
Height | 12.86 in |
Ip Degree Of Protection | front cover IP40 |
Line Rated Current | 400-400 A |
Local Signalling | overload 1 trip indicator green) || 1 trip indicator green) |
Long Time Pick-Up Adjustment Range | 0.4...1 x Ir |
Mercury Free, Pvc Free, Rohs Exemption Information | Yes |
Mounting Mode | unit mount lug) |
Mounting Support | lug |
Net Weight | 32 lb(US) |
Network Frequency | 50/60 Hz |
Number Of Slots | 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in) |
Poles Description | 3P |
Pollution Degree | 3 IEC 60947-1 |
Product Certifications | UL || CSA || NOM |
Product Name | PowerPact P |
Product Or Component Type | circuit breaker |
Quality Labels | CE |
Quantity Per Set | 1 |
Range | PowerPact |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
Standards | UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2 |
Sustainable Offer Status | Green Premium product |
Terminal Identifier | AL800M23K |
Tightening Torque | 50-50 N.m 95-240 mm? (3 x AWG 3/0...3 x 500 kcmil) || 1.0-1.3 N.m |
Trip Unit Name | Micrologic 5.0 |
Trip Unit Technology | electronic, standard, Micrologic 5.0, LSI |
Warranty | 18 months |
Width | 8.27 in |
Wire Stripping Length | 25 mm |