As an Amazon Associate, we earn from qualifying purchases.

Variable speed drive, Altivar Process ATV600, ATV630, cabinet Integration, IP20, 3 kW, 380...480 V, for US | Mayer Electric

Gallery

Attributes

Brand name, Manufacturer name, ManufacturerSQUARE D
DimensionUnitmm
Extra Product NameVariable speed drive, Altivar Process ATV600, ATV630, cabinet Integration, IP20, 3 kW, 380...480 V, for US | Mayer Electric
UPC, MPN, SKUSQDATV630U30N4ZU
Weight3.8
WeightUnitkg
Weight_AttribNet Weight
depth, length196.0
height285.0
height_AttribHeight
jsonUrlData/Product/SQUARE-D-Variable-speed-drive-Altivar-Process-ATV600-ATV630-cabinet-Integration-IP20-3-kW-380-480-V-for-US-SQDATV630U30N4ZU
jsonUrlData2db9bd885-6edb-4f19-ba05-aeea0054cb58
length_AttribDepth
moq, multiple, tierMinQty1, Quantity Per Set1
qtyInStock, Discrete Output Number0
tierPrice10.0
width130.0
width_AttribWidth
Prospective Line Isc50 kA
Product Destinationsynchronous motors || asynchronous motors
Line Current5.8 A 380 V normal duty) || 5.1 A 480 V normal duty) || 4.5 A 380 V heavy duty) || 4 A 480 V heavy duty)
Emc Filterintegrated 10 m EN/IEC 61800-3 category C2 || integrated 50 m EN/IEC 61800-3 category C3 || with EMC plate option
Range Of ProductAltivar Process ATV600
Speed Drive Output Frequency0.1-500 Hz
Asynchronous Motor Control Profilevariable torque standard || constant torque standard || optimized torque mode
Variantstandard version
Ip Degree Of ProtectionIP20IEC 61800-5-1 || IP20IEC 60529
Product Or Component Typevariable speed drive
Apparent Power4.2 kVA 480 V normal duty) || 3.3 kVA 480 V heavy duty)
Motor Power Kw3 kW normal duty) || 2.2 kW heavy duty)
Switching Frequency2...12 kHz adjustable || 4...12 kHz with derating factor
[Us] Rated Supply Voltage380...480 V
Maximum Transient Current8.4 A 60 s heavy duty) || 7.9 A 60 s normal duty)
Communication Port ProtocolEthernet || Modbus TCP || Modbus serial
Discrete Input Logic16 preset speeds
Type Of Coolingforced convection
Continuous Output Current7.2 A 4 kHz normal duty || 5.6 A 4 kHz heavy duty
Product Specific Applicationprocess and utilities
Safety FunctionSTO (safe torque off) SIL 3
Nominal Switching Frequency4 kHz
Maximum Horse Power Rating3 hp heavy duty
Device Short NameATV630
Supply Frequency50...60 Hz - 5...5 %
Synchronous Motor Control Profilepermanent magnet motor || synchronous reluctance motor
Electrical Connectioncontrol removable screw terminals 0.5...1.5 mm? AWG 20...AWG 16 || motor screw terminal 2.5...6 mm? AWG 14...AWG 10 || line side screw terminal 2.5...6 mm? AWG 14...AWG 10
Maximum Output Frequency500 kHz
Height285 mm
Acceleration And Deceleration Rampslinear adjustable separately from 0.01...9999 s
Transmission FrameRTU
Relay Output Number, Analogue Input Number3
Exchange Modehalf duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Data Format8 bits, configurable odd, even or no parity
Power Range2.2-3 kW 380-440 V 3 phase || 2.2-3 kW 480-500 V 3 phase
Phase3 phase
Net Weight3.8 kg
Type Of Polarizationno impedance
Relay Output Typeconfigurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
Frequency Resolutiondisplay unit 0.1 Hz || analog input 0.012/50 Hz
Accuracy+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 ?C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 ?C analog output
Connector TypeRJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
Input CompatibilityDI1...DI6 discrete input level 1 PLC EN/IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC EN/IEC 61131-2
Permissible Temporary Current Boost1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
Motor Slip Compensationcan be suppressed || not available in permanent magnet motor law || adjustable || automatic whatever the load
Mounting Modecabinet mount
Analogue Output Number, Pollution Degree2
Physical InterfaceEthernet || 2-wire RS 485
Minimum Switching Currentrelay output R1, R2, R3 5 mA 24 V DC
Method Of Accessslave Modbus TCP
Refresh Timerelay output R1, R2, R3)5 ms +/- 0.5 ms)
Enclosure Mountingwith heat sink
Isolationbetween power and control terminals
Discrete Input Number8
Local Signallingfor local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
Linearity ErrorAI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
Number Of Addresses1-247 Modbus serial
Width130 mm
Transmission Rate10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Braking To Standstillby DC injection
Depth196 mm
Sampling Duration2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
Rohs Exemption Information, Mercury FreeYes
Environmental DisclosureENVPEP2007009EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65 : WARNING: This product can expose you to chemicals includingLead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX
Circularity ProfileENVEOLI2007009EN
UpgradeabilityUpgraded components available
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Product CertificationsUL || DNV-GL || ATEX INERIS || T?V || ATEX zone 2/22 || CSA
Power Dissipation In Wnatural convection 31 W 380 V 4 kHz || forced convection 78 W 380 V 4 kHz
StandardsUL 508C || EN/IEC 61800-3 || EN/IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || EN/IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Ambient Air Temperature For Operation-15-50 ?C without derating) || 50-60 ?C with derating factor)
Volume Of Cooling Air38 m3/h
Insulation Resistance> 1 MOhm 500 V DC for 1 minute to earth
Shock Resistance15 gn 11 ms IEC 60068-2-27
MarkingCE
Vibration Resistance1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Noise Level54.5 dB 86/188/EEC
Regulation Loopadjustable PID regulator

Distributor offers