As an Amazon Associate, we earn from qualifying purchases.

Variable speed drive, Altivar Process ATV900, ATV930, 55 kW, 400/480 V, with braking unit, IP21 | Mayer Electric

Gallery

Attributes

Brand name, Manufacturer name, ManufacturerMayer Electric Supply
DimensionUnitmm
Extra Product NameVariable speed drive, Altivar Process ATV900, ATV930, 55 kW, 400/480 V, with braking unit, IP21 | Mayer Electric
UPC785901472582
Weight57.5
WeightUnitkg
Weight_AttribNet Weight
depth, length325.5
height922.0
height_AttribHeight
jsonUrlData/Product/SCHNEIDER-ELECTRIC-Variable-speed-drive-ATV930-55kW-400-480V-with-braking-unit-IP21-785901472582
jsonUrlData2ff4fd458-6ef5-4e03-b7f6-abb200c9ccc6
length_AttribDepth
moq, multiple, tierMinQty1, Quantity Per Set1
MPNATV930D55N4
qtyInStock0
SKUSQDATV930D55N4
tierPrice19761.54
width290.0
width_AttribWidth
Prospective Line Isc50 kA
Network Frequency50-60 Hz
Product Destinationasynchronous motors || synchronous motors
Line Current97.2 A 380 V normal duty) || 81.4 A 380 V heavy duty) || 84.2 A 480 V normal duty) || 71.8 A 480 V heavy duty)
Phase3 phase
Asynchronous Motor Control Profileconstant torque standard || optimized torque mode || variable torque standard
Variantwith braking chopper || standard version
Product Or Component Typevariable speed drive
Apparent Power70 kVA 480 V normal duty) || 59.7 kVA 480 V heavy duty)
Ip Degree Of ProtectionIP21
Switching Frequency1...8 kHz adjustable || 2.5...8 kHz with derating factor
Maximum Transient Current127.2 A 60 s normal duty) || 132 A 60 s heavy duty)
Communication Port ProtocolEtherNet/IP || Modbus TCP || Modbus serial
Product Specific Applicationprocess for industrial
Maximum Horse Power Rating75.0 hp normal duty || 60.0 hp heavy duty
Degree Of ProtectionUL type 1
Maximum Output Frequency599 Hz
Range Of ProductAltivar Process ATV900
Motor Power Kw55.0 kW normal duty || 45.0 kW heavy duty
[Us] Rated Supply Voltage380...480 V - 15...10 %
Mounting Modewall mount
Discrete Input Logic16 preset speeds
Continuous Output Current106 A 2.5 kHz normal duty || 88 A 2.5 kHz heavy duty
Nominal Switching Frequency2.5 kHz
Emc Filterintegrated || with EMC plate option
Device ApplicationIndustrial Application
Synchronous Motor Control Profilepermanent magnet motor || synchronous reluctance motor
Power Dissipation In Wnatural convection 131 W 380 V 2.5 kHz || forced convection 917 W 380 V 2.5 kHz
Analogue Output Typesoftware-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
4 Quadrant Operation Possible, With Safety Function Safe Stop 1 (Ss1), With Safety Function Safe Brake Management (Sbc/Sbt), With Safety Function Safe Torque Off (Sto), Brake Chopper Integrated, With Safety Function Safely Limited Speed (Sls)true
Exchange Modehalf duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Local Signallinglocal diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
Data Format8 bits, configurable odd, even or no parity Modbus serial
Relative Symmetric Network Frequency Tolerance5 %
Net Weight57.5 kg
With Safety Function Safe Direction (Sdi), With Safety Function Safe Position (Sp), With Safety Function Safely Limited Position (Slp), With Safety Function Safe Operating Stop (Sos), With Sft Fct Safe Stop 2 (Ss2), With Safety Function Safe Speed Monitor (Ssm), With Safety Function Safe Programmable Logicfalse
Type Of Polarizationno impedance
Relay Output Typeconfigurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 1000000 cycles || configurable relay logic R3 sequence relay NO 1000000 cycles
Analogue Input Number, Relay Output Number3
Motor Slip Compensationautomatic whatever the load || not available in permanent magnet motor law || can be suppressed || adjustable
Discrete Output Number, Analogue Output Number2
Transmission Rate10/100 Mbit/s Ethernet IP/Modbus TCP || 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Method Of Accessslave Modbus TCP
Number Of Addresses1-247
Discrete Input Number10
Linearity ErrorAI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Width290 mm
Depth325.5 mm
Analogue Input TypeAI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Sampling Duration2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Height922 mm
Acceleration And Deceleration Rampslinear adjustable separately from 0.01...9999 s
Maximum Output Voltage480.0 V
Base Load Current At High Overload88.0 A
Transmission FrameRTU
Base Load Current At Low Overload106.0 A
Accuracy+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 ?C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 ?C analog output
Input CompatibilityDI1...DI8 discrete input level 1 PLC EN/IEC 61131-2 || DI7, DI8 pulse input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC EN/IEC 61131-2
Connector Type2 RJ45 || 1 RJ45
Physical InterfaceEthernet || 2-wire RS 485
Minimum Switching Currentrelay output R1, R2, R3 5 mA 24 V DC
Refresh Timerelay output R1, R2, R3)5 ms +/- 0.5 ms)
Isolationbetween power and control terminals
Braking To Standstillby DC injection
Mercury Free, Rohs Exemption InformationYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX
UpgradeabilityUpgraded components available
Environmental DisclosureENVPEP1411014EN
Sustainable Offer StatusGreen Premium product
California Proposition 65 : WARNING: This product can expose you to chemicals includingLead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity ProfileENVEOLI1411014EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Product CertificationsCSA || UL || T?V
Maximum Deflection Under Vibratory Load (During Operation)1.5 mm at 2...13 Hz

Distributor offers

SellerSKUMOQIn stockMultiplePrices
mayerelectric.comSQDATV930D55N4111 @ $9761.54