# PowerLogic HDPM6000 bundle with 168-circuits retrofit modules (2), calibrated for 60 Hz, 480 V | Mayer Electric

**Manufacturer:** SQUARE D  
**MPN:** `SQDMETSEHDPM6168MC`

## Specifications

| Attribute | Value |
| --- | --- |
| Brand name | SQUARE D |
| Manufacturer name | SQUARE D |
| Manufacturer | SQUARE D |
| Extra Product Name | PowerLogic HDPM6000 bundle with 168-circuits retrofit modules (2), calibrated for 60 Hz, 480 V \| Mayer Electric |
| UPC | 3606481986214 |
| jsonUrlData | /Product/SQUARE-D-PowerLogic-HDPM6000-bundle-with-168-circuits-retrofit-modules-2-calibrated-for-60-Hz-480-V-SQDMETSEHDPM6168MC |
| jsonUrlData2 | 42e9d96c-8ebf-44d4-8390-aeea00568080 |
| moq | 1 |
| MPN | SQDMETSEHDPM6168MC |
| multiple | 1 |
| qtyInStock | 0 |
| SKU | SQDMETSEHDPM6168MC |
| tierMinQty1 | 1 |
| tierPrice1 | 12527.48 |
| Network Frequency | 60 Hz |
| Energy Management | asset management \|\| measurement \|\| cost management |
| [Us] Rated Supply Voltage | 24 V DC |
| Power Quality Analysis | total harmonic distortion |
| Variant | equipped |
| Product Or Component Type | multi-circuit energy meter |
| Product Name | PowerLogic HDPM6000 |
| Device Short Name | HDPM6000 |
| Range | PowerLogic |
| Communication Port Support | 2 RJ45 Ethernet \|\| RS485 screw block terminal \|\| I/O bus RJ45 |
| Measurement Accuracy | +/- 1 % |
| Measurement Voltage | 120-120 V AC 60 Hz \|\| 208-208 V AC 60 Hz \|\| 380-380 V AC 60 Hz \|\| 400-400 V AC 60 Hz \|\| 415-415 V AC 60 Hz \|\| 480-480 V AC 60 Hz |
| Sampling Rate | 128 samples/cycle |
| Memory Capacity | 8 GB |
| Communication Port Protocol | TCP/IP \|\| Modbus \|\| SNMP \|\| BACnet |
| Poles Description | 2P + E \|\| 3P + E \|\| 3P + N + E |
| Analogue Input Type | external CT \|\| Rogowski coil |
| Web Services | web page \|\| controller configuration \|\| viewing of captured waveform \|\| real time viewing of data |
| Communication Of Data | power quality \|\| reading of measurements \|\| percentage of load |
| Provided Equipment | retrofit module 2 84-circuit |
| Measurement Category | category III |
| Noise Level | 0-65 dB |
| China Rohs Regulation | X |
| Rohs Exemption Information | Yes |
| Mercury Free | Yes |
| Eu Rohs Directive | Compliant |
| Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
| California Proposition 65 : WARNING: This product can expose you to chemicals including | Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
| Ambient Air Temperature For Operation | -20-60 ?C |
| Mounting Mode | clipped \|\| by screws |
| Ambient Air Temperature For Storage | -40-85 ?C |
| Relative Humidity | 5-90 % |
| Standards | IEC 62443 |
| Mounting Support | 35 mm DIN rail \|\| enclosure |
| Pollution Degree | 2 |
| Type Of Installation | indoor |

## Distributor availability

| Distributor | SKU | Price (USD) | Qty | Stock | MOQ |
| --- | --- | --- | --- | --- | --- |
| mayerelectric.com | SQDMETSEHDPM6168MC | 12527.48 | 1 | None | 1 |

---